Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-1125-02123
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/04/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The air balance report shows that two, 5-ton split-system heat pumps were installed but the approved plans called for two, 3.5-ton split system heat pumps. Provide a revision to the approved construction plans showing the revised HVAC system and revise the heating/cooling load calculations that were used to justify the cooling capacity of the installed heat pump systems. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 11/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |