Permit Number: TC-COM-1125-02123
Parcel: 10707003R

Address:
1109 W GLENN ST

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-1125-02123
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/04/2026 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The air balance report shows that two, 5-ton split-system heat pumps were installed but the approved plans called for two, 3.5-ton split system heat pumps. Provide a revision to the approved construction plans showing the revised HVAC system and revise the heating/cooling load calculations that were used to justify the cooling capacity of the installed heat pump systems.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
11/02/2026 PDSD Application Completeness Express REVIEW COMPLETED