Permit Number: TC-COM-1125-02123
Parcel: 10707003R

Address:
1109 W GLENN ST

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1125-02123
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
11/25/2025 Addressing Validation REQUIRES RESUBMIT The unit number on the permit location (1109) does not match the unit number on the uploaded documents (1105). Please either correct the address on the uploaded documents and resubmit after other reviews are complete or submit a change of address request in the permit sub-records.
Here are instructions on how to withdraw in subrecords: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-an…

If you have questions please contact me at Drew.Szentesy@tucsonaz.gov or contact the Building Official at Building_Official@tucsonaz.gov
12/04/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1125-02123 (1109 W GLENN ST TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. The provided plans are missing Sheet E1.0.
2. Clarify the branch-circuit notations as shown on the Enlarged Electrical Power Plan, REF sheet E2.0. The circuit connections and circuit start points appear to indicate that Multi-Wire Branch Circuits are being used. For instance the notation L1-16,18,20 for office power may indicate a multi-wire branch circuit for power.
3. Multi-wire branch circuits require the following:
210.4(B) Simultaneously disconnect all ungrounded conductors.
240.15(B)(1) Identified handle ties.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/04/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1125-02123 (1109 W GLENN ST TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

a. Show lamps with a maximum of 3500K color temperature, OLC 402.1. Fixture ‘SJ’ is shown with a color temperature of 4000K, which exceeds the maximum allowed.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/26/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-1125-02123
Location: 1109 W GLENN ST
Review Date: 11/26/2025
Site Engineering Comments:
1. The construction plans show the canopy at a height of 22-feet but the associated development package TD-DEV-0223-00141 shows the proposed canopy as 19-feet in height. Revise the commercial building plans to match the associated approved development package. If it is decided that this is the height desired/intended, then a revision to the development package will be required.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
11/24/2025 PDSD Application Completeness Express REVIEW COMPLETED