Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/17/2025 Commercial Mechanical Express REQUIRES RESUBMIT 1. Replacement of commercial HVAC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. Provide the specifications for the proposed new HVAC units.
2. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous HVAC units provided. Reference: Section C503.4, IECC 2018.