Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-1125-02099
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/20/2025 | Commercial Mechanical Express | REQUIRES RESUBMIT | Revised heating/cooling load calculations not supplied. [Initial comment: Provide heating/cooling load calculations that show the total heating and cooling loads for the suite, including the windows, doors, lighting, and ventilation. Provide the heating and cooling capacity of the existing central HVAC unit and the proposed mini-split unit to justify the addition of the proposed mini-split unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018.] | ||
| 11/19/2025 | Addressing Validation | REVIEW COMPLETED | |||
| 11/19/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |