| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/13/2025 | Addressing Validation | REQUIRES RESUBMIT | Site plan missing project address. Resubmit site plan and include complete project address. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf | ||
| 11/17/2025 | Commercial Mechanical Express | REQUIRES RESUBMIT | 1. Provide heating/cooling load calculations that show the total heating and cooling loads for the suite, including the windows, doors, lighting, and ventilation. Provide the heating and cooling capacity of the existing central HVAC unit and the proposed mini-split unit to justify the addition of the proposed mini-split unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 2. Provide the specifications for the proposed mini-split HVAC unit (e.g. manufacturer, model number, heating/cooling capacity, and efficiency ratings). The replacement units shall have an efficiency rating that is greater than or equal to the minimum required by the Department of Energy that went into effect on January 1, 2023, for the Southwest region of the United States. (Beginning on January 1, 2023, the Department of Energy minimum efficiency standards for air conditioning systems was increased from 14.0 to 15.0 SEER using DOE’s pre-2023 appendix M test procedure. Also, all equipment not operational on January 1, 2023, in the Southwest region, must have an Energy Guide label identifying a SEER2 or SEER2/EER2 rating.) 3. Show the size, routing, and termination of the condensate drain for the mini-split unit. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. |
||
| 11/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |