Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-1125-02092
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/13/2025 Commercial Mechanical Express REQUIRES RESUBMIT Provide the specifications for the replacement HVAC units. The units themselves will have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.
11/13/2025 Addressing Validation REVIEW COMPLETED Per customer, work is for unit 140 only.
11/13/2025 PDSD Application Completeness Express REVIEW COMPLETED