Permit Number: TC-COM-1125-02085
Parcel: 13734001D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1125-02085
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2025 Commercial Electrical Standard APPROVED
12/04/2025 Commercial Mechanical Standard APPROVED
12/04/2025 Commercial Plumbing Standard APPROVED
12/04/2025 Site Zoning Standard APPROVED
12/04/2025 Water - PDSD Standard APPROVED
11/13/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
11/13/2025 Site Engineering Standard NOT REQUIRED
12/09/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/09/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1125-02095
ADDRESS: (6701 S RENAISSANCE DR TUCSON, AZ 85746)

COMMENTS:
1. MEANS OF EGRESS PLAN
a. Provide an Egress Plan. Show this information on the Egress Plan.
i. Enter the distance of travel within the facility and their direction of travel.
ii. At the point of exit, enter the required width, the provided width, the distance traveled and the number of occupants exiting.
iii. Show the layout of the space which includes work areas, displays, tables, offices, work tables, everything that help illustrate the actual exit route from the farthest point to the exit discharge.
b. Please amend plans to show the current design occupant load analysis to specify the individual building area of each room or space that is shown on the plan.
i. Further, enter the name of the space, area square footage, clarify the design occupant load (gross or net s.f. per person used) and the number of occupants for each room or space on the plan, in accordance with the requirements of IBC Table 1004. IBC 107.2.7TENT
ii. Yes I agree with your calculation for the retail areas at 108 O.L. (1756 + 4734 = 6490 / 60 = 108 O.L.)
iii. However, the Storage area is completely missed.
1. 1625 + 541 = 2166 / 300 = 7 O.L.
2. Please add this within your code analysis.
3. The total occupant load should be 115 O.L.
2. LAVATORY
a. Lavatory shall be maximum 34 inches above floor to the higher of the rim or counter surface, faucets and soap dispenser shall have a reach depth of 11 inches per ANSI 606.5
b. Metered faucets shall remain open for 10 seconds minimum per ANSI 606.4
a. Water supply and drain pipes under lavatories shall be insulated to protect against contact per ANSI 606.6
3. EXIT THROUGH STORAGE ROOM
a. Egress through intervening spaces. IBC 1016.2 Exception 2 Means of egress are not prohibited through stockrooms in Group M occupancies where all of the following are met.
i. 2.1 The stock is of the same hazard classification as that found in the main retail area.
ii. 2.2 Not more than 50 percent of the exit access is through the stockroom.
iii. 2.3 The stockroom is not subject to locking from the egress side.
iv. 2.4 There is a demarcated, minimum 44-inch-wide aisle defined by full- or partial-height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions.
v. Please clearly show the storage racks/shelves & the demarcated aisle with dimension & marking on the floor such as paint stripes, etc.
4. Cabinetries such as cashier counters.
a. Provide drawings illustrating the following.
b. The tops of work surfaces shall be 28 inches min & 34 inches max above the floor per ICC A117.1 sec 902.4.
c. Sec 306.3.3 Knee clearance shall be 11 inches min in depth at 9 inches above the floor, and 8 inches min in depth at 27 inches above the floor.
d. Sec 306.2.4 Additional toe clearance space extending greater than 6 inches beyond the available knee clearance at 9 inches above the floor.
e. Sec 306.3 Knee clearance shall be 30 inches min in width.
f. 904.3.2 Parallel approach, the counter surface 36 inches min length.
g. 904.3.3 Forward approach, the counter surface 30 inches min length.
2. Please resubmit.
Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
12/08/2025 Fire New Construction Standard REQUIRES RESUBMIT 1. Provide an exiting plan. If the storage area is to be used as a required exit, must comply with 2024 IFC 1016.2 #6.
john.vincent@tucsonaz.gov
5203495581
11/12/2025 PDSD Application Completeness Express REVIEW COMPLETED