Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.5
Permit Number - TC-COM-1125-02080
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/27/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/27/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. The heating/cooling load calculations have been provided but the heating/cooling capacity of the split system is not shown. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the proposed HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2024 and Section 312.1, IMC 2024.] 2. The heating/cooling load calculations do not show the exhaust flowrate of the restroom exhaust fan and the sequence of operation is also not shown. [Initial comment: Provide the exhaust flowrate for the restroom exhaust and the sequence of operation for the exhaust fan (i.e., continuous or intermittent fan operation). Reference: Section 403.3.1.1, IMC 2024.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 10/27/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Comment not resolved. To supply tepid water to a lavatory, a point-of-use instant water heater must be listed to ASSE 1084. [Initial comment: Show how tepid water is being supplied to the lavatory. Reference: Section 607.1, IPC 2024.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 10/21/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |