Review Date Reviewer's Name Type of Review Description Status Comments
12/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/08/2025 Addressing Validation REQUIRES RESUBMIT Site plan incomplete; 1. ADDRESS a. Please confirm with Pima County addressing department (520-724-9512) which address belongs to which space. b. Once confirmed, On the Floor Plan - mark which space is 402 and 404. 2. SEPARATE PERMITS a. Submit a separate permit for each business space. When complete, please resubmit site plan. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: maribel.arevalo@tucsonaz.gov
12/08/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1125-02080
ADDRESS: (402 W AJO WY TUCSON, AZ 85713)

COMMENTS:
1. ADDRESS
a. Please confirm with Pima County addressing department (520-724-9512) which address belongs to which space.
b. Once confirmed, On the Floor Plan - mark which space is 402 and 404.
2. SEPARATE PERMITS
a. Submit a separate permit for each business space.
b. This Permit # TC-COM-1125-02080 can be used for space 402.
i. The City will continue the review for space 402.
c. Submit a separate permit for space 404.
d. Please email me once the second permit is submitted, allowing me to verify and continue reviewing. See my contact email below.
3. The restrooms are not accessible.
a. Please comply to ICC A117.1 requirements.
i. Show the clear floor space on the floor for the water closet.
1. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. ICC A117.1 section 604.3.1
2. Clearance around the water closet shall be 56 inches minimum in depth, measured perpendicular from the rear wall. ICC A117.1 section 604.3.2
ii. No other fixtures (includes the lavatory) or obstructions shall be within the required water closet clearance. ICC A117.1 section 604.3.3
b. Is one water meter shared by the two spaces. Please confirm by entering this information within the Code Analysis..
i. Is there a Utility Joint User Agreement. Please confirm.
ii. Please locate/label on your site plan the location of these meters.
c. Is one sewer waste line shared by the two spaces. Please confirm by entering this information within the Code Analysis..
i. Is there a Utility Joint User Agreement. Please confirm.
ii. Please locate/label the HCS and sewer line to the building on your site plan.
4. Electricity
a. Are there two separate electrical meters, one for each space.
b. Please provide a complete riser diagram that includes these two electrical sub panels.
c. Please provide electrical load calculation.
5. FLOOR PLAN
a. Show the layout of the display cases, cash register counter, etc. on the floor plan.
b. Provide drawings illustrating the following:
i. The tops of work surfaces (cash register) shall be 28 inches min & 34 inches max above the floor per ICC A117.1 sec 902.4.
ii. Sec 306.3.3 Knee clearance shall be 11 inches min in depth at 9 inches above the floor, and 8 inches min in depth at 27 inches above the floor.
iii. Sec 306.2.4 Additional toe clearance space extending greater than 6 inches beyond the available knee clearance at 9 inches above the floor.
iv. Sec 306.3 Knee clearance shall be 30 inches min in width.
v. 904.3.2 Parallel approach, the counter surface 36 inches min length.
vi. 904.3.3 Forward approach, the counter surface 30 inches min length.
6. SIGN
a. Please provide the permit number for the sign installed on the front façade of the business.
7. ELECTRICAL SCHEDULE PANEL B (GUEST HOUSE)
a. Guest House is present on this schedule table.
b. These are commercial businesses.
c. Please correct this guest house item.
8. Please resubmit.
Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
12/18/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1125-02080 (402 W AJO WY TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Outlets shall be tamper resistant per NEC 406.12(A).
2. Clarify panel schedule. Why is it showing as ‘Guest House’?
Plans shall include (as necessary for scope of work), but may not be limited to items below:
3. Provide an electrical demo plan showing all removed unpermitted and unsafe electrical.
4. Provide electrical load calculations, for the Main Panels, Per NEC 220.40.
5. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
6. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
7. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number.
8. Show all GFCI protection (NEC 210.8(B)) in readily accessible location per NEC 210.8.

Additional comments may be forthcoming with complete electrical plans for the building and site.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/29/2025 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1125-02080
ADDRESS/PARCEL: (402 W AJO WY TUCSON, AZ 85713)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:

1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. Show the mechanical exhaust system for the restroom in accordance with IMC 2018 Section 403.2.1(4), including required exhaust airflow rates per Table 403.3.1.1 and the method of control (continuous or automatic).
12/29/2025 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1125-02080
ADDRESS/PARCEL: (402 W AJO WY TUCSON, AZ 85713)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:

1. Please show the existing water distribution piping, including pipe sizes and routing. Also show the size of the water meter serving this building. Reference: Section 107.2.1, IBC 2018.
2. Please show the existing sanitary sewer piping, including pipe sizes, routing, and points of connection. Reference: Section 107.2.1, IBC 2018.
3. Lavatories are required to be provided with hot and cold water. Please show an approved hot water source and temperature-limiting device. Reference: Section 607.1, IPC 2018.
12/04/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-1125-02080
402 W. Ajo Wy. Tucson, AZ 85713
Certificate of Occupancy Smoke Shop (1st Review)

TRANSMITTAL DATE: 12/4/2025

This site is located in the C-2 zone (UDC 4.7.21). Smoke shop is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.9.H.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Prior to obtaining a Certificate of Occupancy, a Zoning Compliance Letter will be required to determine whether the proposed use (Smoke Shop) is allowed at this location. The letter is a separate request and must be obtained through your TDC Online account. Please include this letter with your resubmittal documents.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.