Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1125-02077
Parcel: 12407174A

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1125-02077
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2025 Commercial Electrical Standard APPROVED
12/03/2025 Commercial Plumbing Standard APPROVED
12/03/2025 Water - PDSD Standard APPROVED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
12/03/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
11/24/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1125-02077 (750 E BROADWAY BL TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

a. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
This will require all exterior lights to be shown on the site exterior lighting plan, including site and parking lot lights, and lights for other buildings as covered by the associated Development Package. >>> Plan is missing the required Lumen calculations. >>> Lighting fixture G is new. Must meet OLC.
b. List the Lighting Area per OLC (E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
c. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
d. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
e. Show lamps with a maximum of 3500K color temperature, OLC 402.1. Multiple exterior lighting fixtures are shown with a CCT greater than the max allowed.
f. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
g. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

h. Specify any exceptions used.

i. Provide Curfew lighting controls If applicable Per section 403.



Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/13/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-1125-02077
Location: 750 E BROADWAY BL
Review Date: 11/13/2025
Site Engineering Comments:
1. The proposed exterior entry updates and parking additions for this commercial property requires the submission of a Development Package. Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.
2. Site Engineering is unable to review and approve permit TC-COM-1125-02077 until the associated Development Package is reviewed and approved by all reviewers.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
12/04/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-1125-02077
750 E. Broadway Blvd. Tucson, AZ 85719
Interior TI w/ new exterior entry ramp (1st Review)

TRANSMITTAL DATE: 12/4/2025

This site is located in the C-3 (UDC 4.7.22) and I-1 (4.7.29) zones.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: As you are proposing new exterior parking and a new entrance ramp/stairs on an existing commercial site, a Development Package (DP) that meets the requirements of the Checklist for Minor Changes to Commercial/Industrial Site is required to be submitted and approved. This DP is a separate submittal from the building plans and must be approved by all reviewers prior to approval of the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
11/12/2025 PDSD Application Completeness Express REVIEW COMPLETED