Permit Number: TC-COM-1125-02057
Parcel: 13419044A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-1125-02057
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2025 Commercial Electrical Express NOT REQUIRED
11/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2025 Addressing Validation REQUIRES RESUBMIT Please update this permit application to show this permit is for 209 S Kolb.
How to submit CHANGE OF ADDRESS:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
11/14/2025 Outdoor Lighting Express REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1125-02057 (211 S KOLB RD TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:

a. Provide the Lumen output and the color temperature of the outdoor lighting fixture being replaced. List if this lighting fixture is full-cutoff or unshielded. (see OLC chapter 2 definitions).
b. You need to show that the total lumen count after the repairs and replacements is less than or equal to what was existing. Show the existing lumen values of the lights repaired or replaced and show the lumen values of the new light fixtures.
c. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
d. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
e. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).

f. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/14/2025 PDSD Application Completeness Express REVIEW COMPLETED