Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-1125-02046
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2025 | Commercial Electrical Express | APPROVED | |||
| 11/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/10/2025 | Commercial Mechanical Express | REQUIRES RESUBMIT | 1. Replacement of the AC unit for unit 3 of the duplex will require a heating/cooling load calculation to justify the capacity of the units being installed (Sections R403.7, IECC 2018). 2. Provide the specifications for the replacement HVAC unit (e.g. manufacturer, model number, heating/cooling capacity, and efficiency ratings). The replacement units shall have an efficiency rating that is greater than or equal to the minimum required by the Department of Energy that went into effect on January 1, 2023. |
||
| 11/06/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |