Permit Number: TC-COM-1125-02025
Parcel: 112054100

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-1125-02025
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2025 Commercial Plumbing Express APPROVED
12/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/03/2025 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1125-02025 (2970 N CAMPBELL AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Provide a panel schedule highlighting the circuits that are being modified and added. Correlate the panel schedule circuit numbers with the location of the electrical outlets, receptacles, switches, mechanical equipment, transformers, etc, (for the new heaters) on the electrical plan.
2. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/03/2025 Commercial Mechanical Express REQUIRES RESUBMIT Provide the specifications for the proposed gas-fired patio heaters. Include the required clearances and exhaust requirements. Reference: Sections 301 and 304.1, IMC 2018 and Section 503.1, IFGC 2018.
12/02/2025 PDSD Application Completeness Express REVIEW COMPLETED