Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-1125-02025
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2025 | Commercial Electrical Express | APPROVED | |||
| 12/08/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/08/2025 | Commercial Mechanical Express | REQUIRES RESUBMIT | The manufacturer’s specification show that the minimum manifold pressure for the heaters is 7” WG. Verify that the meter will have a minimum supply pressure of 2 PSIG with appropriate pressure regulation to serve all of the existing and proposed gas-fired appliances. Provide a detail showing the installation of a sediment trap for each heater. Reference: Sections 402.6 and 408.4, IFGC 2018. [Initial comment: Provide the specifications for the proposed gas-fired patio heaters. Include the required clearances and exhaust requirements. Reference: Sections 301 and 304.1, IMC 2018 and Section 503.1, IFGC 2018.] | ||
| 12/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |