Permit Number: TC-COM-1125-02025
Parcel: 112054100

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-1125-02025
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2025 Commercial Electrical Express APPROVED
12/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/08/2025 Commercial Mechanical Express REQUIRES RESUBMIT The manufacturer’s specification show that the minimum manifold pressure for the heaters is 7” WG. Verify that the meter will have a minimum supply pressure of 2 PSIG with appropriate pressure regulation to serve all of the existing and proposed gas-fired appliances. Provide a detail showing the installation of a sediment trap for each heater. Reference: Sections 402.6 and 408.4, IFGC 2018. [Initial comment: Provide the specifications for the proposed gas-fired patio heaters. Include the required clearances and exhaust requirements. Reference: Sections 301 and 304.1, IMC 2018 and Section 503.1, IFGC 2018.]
12/04/2025 PDSD Application Completeness Express REVIEW COMPLETED