Permit Number: TC-COM-1125-02025
Parcel: 112054100

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4

Permit Number - TC-COM-1125-02025
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/23/2025 Commercial Mechanical Express REQUIRES RESUBMIT The manufacturer’s required minimum inlet pressure for the specified infra-red patio heaters is 7” WC. If you choose not to raise the system pressure to enable the inlet pressure to comply with the manufacturer’s published installation instructions, you will need to select a patio heater that will operate at a lower natural gas pressure. Reference: Section 402.3, IFGC 2018. [Second comment: The manufacturer’s specification show that the minimum manifold pressure for the heaters is 7” WG. Verify that the meter will have a minimum supply pressure of 2 PSIG with appropriate pressure regulation to serve all of the existing and proposed gas-fired appliances. Provide a detail showing the installation of a sediment trap for each heater. Reference: Sections 402.6 and 408.4, IFGC 2018.] [Initial comment: Provide the specifications for the proposed gas-fired patio heaters. Include the required clearances and exhaust requirements. Reference: Sections 301 and 304.1, IMC 2018 and Section 503.1, IFGC 2018.]
12/23/2025 PDSD Application Completeness Express REVIEW COMPLETED