Permit Number: TC-COM-1124-02272
Parcel: 13811073D

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1124-02272
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
12/04/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The scope of work states, "Installing new 100 amp disconnect and new meter socket for future use”.

The plans show a new 200 amp meter/electric service disconnect and panel. Please revise the drawing and or revise the scope of work description to correlate with the plans.

2 The site plan and panel schedule shows the new panel identified as ‘Panel 240’. The electrical line diagram shows the new panel identified as ‘New Panel 235’. Please clarify and revise the plans as necessary.

REf; 2018 IBC section 107.2.1, 2017 NEC.
12/02/2024 PDSD Application Completeness REVIEW COMPLETED