Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1124-02272
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/04/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/04/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The scope of work states, "Installing new 100 amp disconnect and new meter socket for future use”. The plans show a new 200 amp meter/electric service disconnect and panel. Please revise the drawing and or revise the scope of work description to correlate with the plans. 2 The site plan and panel schedule shows the new panel identified as ‘Panel 240’. The electrical line diagram shows the new panel identified as ‘New Panel 235’. Please clarify and revise the plans as necessary. REf; 2018 IBC section 107.2.1, 2017 NEC. |
||
12/02/2024 | PDSD Application Completeness | REVIEW COMPLETED |