Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1124-02264
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2024 | Commercial Electrical | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 12/10/2024 9:19:36 AM 1. E1.1: Key Notes have 2 distinct #3 Key Notes. 2. E1.1: Key Notes E18-E20 are of a different format on the drawing than Key Notes 1-16. 3. E1.1: Could not locate Key Note 17. 4. E2.1: Keyed Notes missing number identification. Could not locate Keyed Note 11. |
||
| 12/31/2024 | Water - PDSD | APPROVED | |||
| 12/31/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/19/2024 | Commercial Building | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 12/19/2024 7:00:59 PM 1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2. GENERAL - GEOTECHNICAL REPORT: Please provide a copy of the site-specific geotechnical report referenced on the structural general notes, Sheet S4.0. The report should support the appropriateness of the selected foundation system for the project site. All building code references must be updated to the current code adopted by the City. 3. GENERAL - SPECIAL INSPECTIONS: The notes on Special Inspections included on Sheets S4.0 and SSD1 do not meet the requirements for a Statement of Special Inspections as outlined in the 2018 International Building Code Section 1704.3.1. A complete statement must include the following information. Please update the structural general notes accordingly, making sure to reference the correct edition of the code as part of the revision (2018 IBC). i. The materials, systems, components required to have special inspections - DONE ii. The type and extent of each special inspection as outlined in IBC Section 1705 iii. For each type of special inspection, identification as to whether it will be continuous or periodic as defined by the 2018 IBC 4. SHEET SD1 - MISSING INFORMATION, REFUSE ENCLOSURE: Information on the design of the foundation for the Refuse Enclosure appears incomplete. A plan note on Enlarged Plan 9/SD1 calls for the enclosure to be supported on a steel-reinforced concrete apron. Section Cut 4/SD1 shows the concrete slab and a continuous wall footing, but refers to "Structural" for the footing dimensions and information on reinforcement. Please confirm where this information has been provided. 5. SHEET SD2 - MISSING INFORMATION, PARKING SCREEN WALL: Civil Detail 6/SD2 shows a parking screen wall and refers to the structural drawings for information on the foundation and CMU reinforcement. Please confirm where this information has been provided. 6. SHEED SD4 - MISSING INFORMATION, SIGNAGE FOUNDATIONS: Civil Sheet SD4 includes foundation designs for multiple site structures and signage. However, the Order Canopy, which has the longest cantilevered element, does not have a foundation design included. Please indicate how this structure is being supported at grade. 7. SHEET S1.2 - KITCHEN HOODS: The Mechanical Sheets M1.2 and M4.1 indicate four proposed Kitchen Hoods, KH1 through KH4, to be suspended from roof framing. Weights of these units have not been included on the mechanical schedules. Please coordinate the location and operating weights of these units and include them on the Structural Roof Plan to confirm they have been included in design of the typical roof joists. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 12/10/2024 3:51:23 PM |
||
| 12/19/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 12/16/2024 10:55:38 AM 1. General - Provide heat load Calculations. Show all O/A loads on calculations. - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads. |
||
| 12/19/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 12/15/2024 5:53:17 PM First Plumbing Review: 1). Plan Page M1.4: Gas sizing code year is incorrect: Change Code year to 2018 IFGC 2). Plan Pages P1.0 & P2.0: Missing shut off valves at main water entrance & each hose bib. Add shut off valves at main water entrance & at each hose bib. -2018 IPC 606.1, 606.2 3). Plan Page P2.1: Restroom sanitary/venting configurations are not clear & lavatories appear to be missing. Update Restroom sanitary/venting configurations to be clear on each fixture is connecting to the sanitary & venting system. -2018 IPC 901.2.1 4). Plan Page P3.0: Missing Floor Drain Trap primer detail. Add floor drain trap primer detail. -2018 IPC 1002.4.1 5). Plan Page P4.1: Missing Floor drain trap primer note on plan page P4.1 Fixture schedule. Add Floor drain trap primer note to plan page P4.1 Fixture schedule. -2018 IPC 1002.4.1 6). Plan Page T1.0: Missing Occupancy load plumbing fixture count summary. Add Occupancy load plumbing fixture count summary. -2018 IPC 403.1 |
||
| 12/26/2024 | Site Engineering | REQUIRES RESUBMIT | 1. The associated development package TD-DEV-1124-00319 must be approved before this building permit can be approved. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
| 12/31/2024 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Fernando Garcia Planning & Development Services Department – Zoning Review Section PROJECT: TC-COM-1124-02264 – Commercial Building (ref. TD-DEV-1124-00319) APN 140-36-3550 85705 Plan Review (2nd Review) TRANSMITTAL DATE: December 31, 2024 This site is zoned PAD-21. Food service is an approved used in this zone. 1. (Comment) Although the plans appears to match, final Site Zoning approval of this plan cannot occur until development package, TD-DEV-1124-00319, is approved. Once approved, please resubmit the building permit. Ensure the building permit documents match the approved development package (for example, inclusion, of new shade structures). RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approval of TD-DEV-1124-00319 and resubmittal of revised plans. If you have any questions about this transmittal, please contact Fernando L. Garcia at fernando.garcia2@tucsonaz.gov. | ||
| 12/23/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 12/05/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |