Permit Number: TC-COM-1124-02258
Parcel: 10607004C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-1124-02258
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/15/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide a code analysis and for this structure and use to include, but not be limited to: IBC 107.2.1
A. The Currently adopted Governing Codes
B. The Occupancy and Use
C. The Type of Construction
D. Indicate if there are Fire Sprinklers
E. The Building Area
F. Number of Occupants and Occupant Load Factor used
G. Number of exits required, and the number provided
H. Plumbing fixtures required and the plumbing fixtures provided
2. Please provide an existing building plan, a demolition plan and a new construction plan to show the work taking place to convert the space from a nail saloon to a barber shop. IBC 107.2.1
3. Please keep in mind; IEBC 305.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. If these items are in full compliance with the current code, provide a statement indicating this on the cover sheet of the drawings. Otherwise, accessibility upgrades shall be required in accordance with IEBC.305.7.

1. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. If this exemption is taken, accessibility upgrades equaling 20% of the cost of the project shall be made.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
01/21/2025 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Fernando Garcia
Planning & Development Services Department – Zoning Review Section

PROJECT:
TC-COM-1124-02258
1015 W Prince Rd, Unit 161, Tucson, AZ 85705
Plan Review (4th Review)

TRANSMITTAL DATE: January 21, 2025

For faster Site Zoning review on resubmittal, please alert fernando.garcia2@tusconaz.gov.

This site is zoned C-1 (UDC Section 4.7.20). Personal Service (Barber Shop) is a permitted use in this zone.

1. (COMMENT) A certificate of occupancy requires both a building code and zoning code analysis. Follow guidance from the Commercial Building Review Mark Masek for the building code analysis.

Also provide a zoning code analysis on the next site plan. The zoning for this site is “C-1”. The proposed zoning code use for this site is: “Commercial Services Use Group – Personal Services (Barber Shop)”. Please indicate this as the “UDC (Zoning Code) Use” on the next plans. Also cite the current zoning.

2. (Comment) Annotate gross floor area (GFA) of the suite.

3. (Comment) Per the Pima County Assessor's Office, the correct legal description for this parcel is "E193.02' W693.02' N2 N2 NE4 SW4 EXC S50' EXC N45' 1.04 AC SEC 26-13-13"

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Resubmittal of revised plans and a comment response letter indicating responses to reviewer comments.

If you have any questions about this transmittal, please contact Fernando L. Garcia at fernando.garcia2@tucsonaz.gov.
01/07/2025 Fire New Construction REVIEW COMPLETED
12/31/2024 PDSD Application Completeness Express REVIEW COMPLETED