Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-1124-02254
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/09/2025 | Commercial Building | APPROVED | |||
01/09/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
01/09/2025 | Commercial Mechanical | REQUIRES RESUBMIT | This was requested on the first review and is requested again. Please provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C502.2.3, IECC 2018. | ||
01/09/2025 | Commercial Plumbing | REQUIRES RESUBMIT | This was requested on the first review and is requested again. 1. Please provide a site drawing showing the building footprint, the property lines, the location of the grease interceptor, and the connection of the building sewer to the public sewer. Reference: Section 107.2.1, IBC 2018. | ||
12/26/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |