Permit Number: TC-COM-1124-02244
Parcel: 11901072A

Address:
214 E BENSON HY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02244
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/23/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend plans as the designer’s seal, signature, and date signed is required on all sheets. IBC 107.1 For example, this is missing from the structural pages.
2. Provide the structural calculations prepared by an Arizona licensed design professional, used to design this building and the foundation. IBC 107.2.1
3. Provide a statement of special inspections statement of special inspections in accordance with Section 1704.3.
4. Provide a list of the required special inspections on the design drawings. IBC 107.2.1
5. Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
6. Please amend the plans to provide Mechanical and Plumbing plans with next review in accordance with SECTION 107 of the 2018 IBC and the PDSD Building Plan Requirements, complete set of fully dimensioned plans demonstrating the full scope of work shall be provided. IBC107.2.1
7. Provide the plumbing fixtures as required by IBC Table 2902.1 or submit an Appeal to the Building Official for an alternate materials, design and methods used to comply with the code. IBC 104.11
8. Please amend plans to provide landings at doors with a width not less than the width of the door. whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. Landings shall have a length measured in the direction of travel of not less than 44 inches. IBC 1010.1.6
10. Please amend plans to demonstrate compliance with the accessibility requirements of IBC Chapter 11
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
12/23/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
1 Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting on the Parcel. See Chapter 204 for plan submittal requirements.
2 Provide compliance with the 2018 IECC for the lighting.
Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC).
12/23/2024 Commercial Mechanical REQUIRES RESUBMIT
12/23/2024 Commercial Plumbing REQUIRES RESUBMIT
12/26/2024 Fire New Construction REQUIRES RESUBMIT Resolve Commercial Building comments.
Questions: patricia.shelton@tucsonaz.gov
12/26/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Fernando Garcia
Planning & Development Services Department – Zoning Review Section

PROJECT:
TC-COM-1124-02244 – Commercial Building
214 E Benson Hy Tucson, AZ 85713
Plan Review (1st Review)

TRANSMITTAL DATE: December 26, 2024

This site is zoned C-2 (UDC Section 4.7.21). Commercial storage is a permitted use in the C-2 zone subject to use-specific standard 4.9.10.A.

1. (Comment) Per UDC Section 3.3.3.G, a development package is required to be submitted and approved prior to the approval of this commercial building permit. Section 3.3.3.G requires a development package when there is “new non-residential development” or “reconfiguration of an area outside a building” as in this case.

A development package must be stamped by an architect or engineer registered in Arizona. See requirements for a development package at the following link: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Development-Package.

The DP site plan should include all structures on site, including shade structure or sails, shed, and storage containers.

2. (Comment) The new storage building constitutes an expansion of over 25% in gross floor area. As such, the site must come into compliance with current development standards for motor vehicle parking, bicycle parking, landscaping/screening, native plant preservation, access, pedestrian circulation, detention/retention, waste disposal, and commercial rainwater harvesting as articulated in UDC Section 7, UDC TSM Section 7, UDC TSM Section 8, and UDC TSM Section 10. These will need to be reflected on the development package.

3. (Comment) Once the submitted development package is approved, please resubmit the building permit. Ensure the building permit documents match the approved development package (for example, inclusion, of new shade structures).

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approval of development package or development package revision, and resubmittal of revised plans.

If you have any questions about this transmittal, please contact Fernando L. Garcia at fernando.garcia2@tucsonaz.gov.
12/04/2024 PDSD Application Completeness Express REVIEW COMPLETED
12/24/2024 Site Engineering REVIEW COMPLETED