Permit Number: TC-COM-1124-02238
Parcel: 121070140

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1124-02238
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2025 Commercial Electrical APPROVED
02/04/2025 Commercial Mechanical APPROVED
02/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/04/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Provide specifications for the hydromechanical grease interceptor for sink 28 along with a detail showing how the interceptor will be installed. [Initial comment: The double-bowl hand sink (28) shall be directly connected to the sanitary drainage system. If the sink will also be used for food preparation or dishwashing, it must be connected to the grease waste system. Reference: Sections 301.3 and 1003.3, IPC 2018.]
2. Hand washing sink, 27, shall be individually trapped. Only combination fixtures are allowed to be served by a single trap. Reference: Section 1002.1, exception 2, IPC 2018.
01/15/2025 Fire New Construction REVIEW COMPLETED 1.Fire alarm, fire sprinklers, kitchen fire supresion and Co2 System requires a separate submittal and permit.
2. Co2 system requires an operational permit
3. Install Fire extinguishers as required per the 2024 IFC Section 906
01/13/2025 PDSD Application Completeness Express REVIEW COMPLETED