Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-1124-02238
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2025 | Commercial Electrical | APPROVED | |||
| 02/04/2025 | Commercial Mechanical | APPROVED | |||
| 02/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/04/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide specifications for the hydromechanical grease interceptor for sink 28 along with a detail showing how the interceptor will be installed. [Initial comment: The double-bowl hand sink (28) shall be directly connected to the sanitary drainage system. If the sink will also be used for food preparation or dishwashing, it must be connected to the grease waste system. Reference: Sections 301.3 and 1003.3, IPC 2018.] 2. Hand washing sink, 27, shall be individually trapped. Only combination fixtures are allowed to be served by a single trap. Reference: Section 1002.1, exception 2, IPC 2018. |
||
| 01/15/2025 | Fire New Construction | REVIEW COMPLETED | 1.Fire alarm, fire sprinklers, kitchen fire supresion and Co2 System requires a separate submittal and permit. 2. Co2 system requires an operational permit 3. Install Fire extinguishers as required per the 2024 IFC Section 906 |
||
| 01/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |