Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.1
Permit Number - TC-COM-1124-02238
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2025 | Commercial Building Standard | APPROVED | |||
| 04/17/2025 | Commercial Electrical Standard | APPROVED | |||
| 04/28/2025 | Commercial Plumbing Standard | APPROVED | |||
| 04/24/2025 | Site Zoning Standard | APPROVED | |||
| 04/28/2025 | Water - PDSD Standard | APPROVED | |||
| 04/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/28/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | The minimum Annual Walk-in Energy Factor (AWEF) for a medium temperature, indoor cooler is 5.61 BTU/W-h. The proposed unit has an AWEF of 3.2 BTU/W-h. Reference: Section C403.10.2.1, IECC 2018. | ||
| 04/17/2025 | Fire New Construction Standard | REVIEW COMPLETED | 1. The Walk in cooler needs fire sprinklers coverage under separate permit. 2. The CO2 system needs a separate operational permit. |
||
| 04/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |