Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1124-02238
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2025 Commercial Building Standard APPROVED
04/17/2025 Commercial Electrical Standard APPROVED
04/28/2025 Commercial Plumbing Standard APPROVED
04/24/2025 Site Zoning Standard APPROVED
04/28/2025 Water - PDSD Standard APPROVED
04/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/28/2025 Commercial Mechanical Standard REQUIRES RESUBMIT The minimum Annual Walk-in Energy Factor (AWEF) for a medium temperature, indoor cooler is 5.61 BTU/W-h. The proposed unit has an AWEF of 3.2 BTU/W-h. Reference: Section C403.10.2.1, IECC 2018.
04/17/2025 Fire New Construction Standard REVIEW COMPLETED 1. The Walk in cooler needs fire sprinklers coverage under separate permit.
2. The CO2 system needs a separate operational permit.