Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1124-02233
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/17/2024 | Commercial Building | APPROVED | |||
| 12/26/2024 | Site Zoning | NOT REQUIRED | |||
| 12/26/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/18/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response 1 Please assign a circuit and panel designation for each electrical device, lighting, and mechanical, plumbing appliances on the electrical floorplans. Correlate with the panel schedule directory. 2 Fill in the missing information at the bottom of the panel schedule. REF; 2018 IBC section 107.2.1, 2017 NEC 408.4, City of Tucson Commercial Plan Submittal Requirements. |
||
| 12/17/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 12/02/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 12/23/2024 | Site Engineering | REVIEW COMPLETED |