Permit Number: TC-COM-1124-02217
Parcel: 10408005D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-1124-02217
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/03/2025 Commercial Mechanical REQUIRES RESUBMIT Supplying 30 CFM to the IT room will result in only about 2 CFM of outside air reaching the IT room, based on a total of 1400 CFM from RTU-4 and 96 CFM of outside air supplied by the unit. Also, the balancing data on the mechanical plan identifies only 1180 CFM being delivered by RTU-4. Increase the total supply air from RTU-4 and the supply air to the IT room to ventilate the IT room and to prevent coil freeze-up of RTU-4. [Second comment: The Outside Air Calculations calls for the IT room to receive outside air from RTU-4 but the plans show no connection between RTU-4 and the IT room. Show how the IT room will be ventilated.] [Initial comment: How is the IT room being ventilated? Reference: Section 401.2, IMC 2018.]
06/10/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-1124-02217
4695 N ORACLE RD Unit: 117 – C-3
Marijuana Facility: Dispensary (2nd Review)

TRANSMITTAL DATE: June 10, 2025

Resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-3 zone (UDC 4.7.22). Marijuana Facility: Dispensary is a permitted uses in this zone (Table 4.8-4), subject to a Mayor and Council Special Exception Procedure, Section 3.4.4 and Use Specific Standards 4.9.9.E.1.

1. Until the Special Exception is approved by all review agencies Zoning cannot approve this plan. As an expansion is proposed a Mayor and Council Special Exception Procedure, Section 3.4.4 must be submitted and approved prior to approval of this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/02/2025 PDSD Application Completeness Express REVIEW COMPLETED