Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-1124-02217
Parcel: 10408005D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-1124-02217
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2025 Commercial Building APPROVED
05/08/2025 Commercial Plumbing APPROVED
05/08/2025 Water - PDSD APPROVED
05/08/2025 Site Engineering NOT REQUIRED
05/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/08/2025 Commercial Mechanical REQUIRES RESUBMIT 1. The revised Air Balance Schedule now shows that the total suite will have 433 CFM of excess air. If only the exhausted air is being filtered through a charcoal filter, how will this allow for mitigation of the odor spread by the air exiting the suite when the doors open? [Initial comment: The balancing information shows that the Phase 2 area will have 294 CFM of air entering the suite with no exhaust. Combining phases 1 and 2, the total space will have 549 CFM of excess outside air. Provide a design that will ensure that the facility will comply with the odor mitigation requirements enforced by the Zoning Department. ]
2. The Outside Air Calculations calls for the IT room to receive outside air from RTU-4 but the plans show no connection between RTU-4 and the IT room. Show how the IT room will be ventilated. [Initial comment: How is the IT room being ventilated? Reference: Section 401.2, IMC 2018.]
05/12/2025 Site Zoning REQUIRES RESUBMIT CDRC Transmittal

FROM: Loran Shamis, Principal Planner
PDSD Zoning Review Section

PROJECT: TC-COM-1124-02213
Tenant Improvement – Marijuana Dispensary expansion (2nd Review)
4695 N Oracle Unit: 117

TRANSMITTAL DATE: May 12, 2025

DUE DATE: May 7, 2025

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

01. COMMENT: The proposed scope of work is the expansion of a Marijuana Dispensary, which is permitted through a Mayor and Council Special Exception Procedure. Zoning cannot approve until the Mayor and Council Special Exception Procedure has been approved.
02. COMMENT: Clearly demonstrate that all requirements of UDC Article 4.9.9.E.1 are met. The odor mitigation plan will be reviewed in collaboration with City of Tucson Commercial Building Mechanical review to ensure consistency.

For questions regarding Zoning comments, please contact me at: Loran.Shamis@tucsonaz.gov
05/05/2025 Fire New Construction REVIEW COMPLETED Alterations to the fire alarm or fire sprinklers system requires a separate submittal and permit.
04/23/2025 PDSD Application Completeness Express REVIEW COMPLETED