Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-1124-02213
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/03/2025 | Commercial Plumbing | APPROVED | |||
| 06/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/03/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Keynote 5 on M2.1 still calls for the exhaust fan to be interlocked with the light switch. [Second comment: Revise Keynote 5 on M2.1 to agree with note 2 of the Exhaust Fan Schedule. [Initial comment: Revise the airflow rate and sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.] | ||
| 06/10/2025 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review PROJECT: TC-COM-1124-02213 4695 N ORACLE RD Unit: 115 – C-3 Marijuana Facility: Dispensary (2nd Review) TRANSMITTAL DATE: June 10, 2025 Resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-3 zone (UDC 4.7.22). Marijuana Facility: Dispensary is a permitted uses in this zone (Table 4.8-4), subject to a Mayor and Council Special Exception Procedure, Section 3.4.4 and Use Specific Standards 4.9.9.E.1. 1. Until the Special Exception is approved by all review agencies Zoning cannot approve this plan. As an expansion is proposed a Mayor and Council Special Exception Procedure, Section 3.4.4 must be submitted and approved prior to approval of this plan. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 06/02/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |