Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1124-02208
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/10/2024 | Site Zoning | APPROVED | |||
| 12/10/2024 | Water - PDSD | APPROVED | |||
| 12/10/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/18/2024 | Commercial Electrical | REQUIRES RESUBMIT | Structural(S) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:46 AM 1. Special Inspections Intermediate Certificate ◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Sheet G001 states that registered design professional shall specify special inspections requirements but missing from the construction plan. Also missing special inspection certification documents with signatures. ◦ You may obtain the form at the following link: ◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf ◦ The Condition is added to the permit and then satisfied upon approval of the form. 2. 2018 California Building Code is referenced and used in structural calculation for City of Tucson, AZ project. (Applicable codes and references) 3. A702 – Detail 12 shows new concrete slab but such drawing is missing to show scope of work (2018 International Building Code section 107.2.1). Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:06:05 AM 1. Sheet G001/G002 – Adopted building codes missing applicable accessibility code for City of Tucson. 2. A101 - Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7). 3. A702 – Detail 11 is using 3x6 wood blocking for construction type ll-B noncombustible building. Explain and provide such applicable code exception section. 4. A703 – Partition detail 1 reference A101 for wall material specifications but missing from that sheet. 5. General – Provide response narrative to each review comments: building, structural, MPE, etc. Mechanical(M) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:27 AM 1. Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7). 2. M201 – Existing roof top units indicated but missing roof plan. Electrical(E) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:04:45 AM 1. E203 – Identify all cross reference electrical details in power or lighting plan such as typical slab penetration detail. This is described as one-story structure. Plumbing(P) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:05 AM 1. Missing P102 new above ground plumbing plan listed in drawing index. 2. P201 – Residential code sections referenced in plumbing specifications. |
||
| 11/18/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Structural(S) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:46 AM 1. Special Inspections Intermediate Certificate ◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Sheet G001 states that registered design professional shall specify special inspections requirements but missing from the construction plan. Also missing special inspection certification documents with signatures. ◦ You may obtain the form at the following link: ◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf ◦ The Condition is added to the permit and then satisfied upon approval of the form. 2. 2018 California Building Code is referenced and used in structural calculation for City of Tucson, AZ project. (Applicable codes and references) 3. A702 – Detail 12 shows new concrete slab but such drawing is missing to show scope of work (2018 International Building Code section 107.2.1). Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:06:05 AM 1. Sheet G001/G002 – Adopted building codes missing applicable accessibility code for City of Tucson. 2. A101 - Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7). 3. A702 – Detail 11 is using 3x6 wood blocking for construction type ll-B noncombustible building. Explain and provide such applicable code exception section. 4. A703 – Partition detail 1 reference A101 for wall material specifications but missing from that sheet. 5. General – Provide response narrative to each review comments: building, structural, MPE, etc. Mechanical(M) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:27 AM 1. Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7). 2. M201 – Existing roof top units indicated but missing roof plan. Electrical(E) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:04:45 AM 1. E203 – Identify all cross reference electrical details in power or lighting plan such as typical slab penetration detail. This is described as one-story structure. Plumbing(P) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:05 AM 1. Missing P102 new above ground plumbing plan listed in drawing index. 2. P201 – Residential code sections referenced in plumbing specifications. |
||
| 11/18/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Structural(S) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:46 AM 1. Special Inspections Intermediate Certificate ◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Sheet G001 states that registered design professional shall specify special inspections requirements but missing from the construction plan. Also missing special inspection certification documents with signatures. ◦ You may obtain the form at the following link: ◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf ◦ The Condition is added to the permit and then satisfied upon approval of the form. 2. 2018 California Building Code is referenced and used in structural calculation for City of Tucson, AZ project. (Applicable codes and references) 3. A702 – Detail 12 shows new concrete slab but such drawing is missing to show scope of work (2018 International Building Code section 107.2.1). Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:06:05 AM 1. Sheet G001/G002 – Adopted building codes missing applicable accessibility code for City of Tucson. 2. A101 - Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7). 3. A702 – Detail 11 is using 3x6 wood blocking for construction type ll-B noncombustible building. Explain and provide such applicable code exception section. 4. A703 – Partition detail 1 reference A101 for wall material specifications but missing from that sheet. 5. General – Provide response narrative to each review comments: building, structural, MPE, etc. Mechanical(M) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:27 AM 1. Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7). 2. M201 – Existing roof top units indicated but missing roof plan. Electrical(E) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:04:45 AM 1. E203 – Identify all cross reference electrical details in power or lighting plan such as typical slab penetration detail. This is described as one-story structure. Plumbing(P) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:05 AM 1. Missing P102 new above ground plumbing plan listed in drawing index. 2. P201 – Residential code sections referenced in plumbing specifications. |
||
| 11/18/2024 | Commercial Structural | REQUIRES RESUBMIT | Structural(S) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:46 AM 1. Special Inspections Intermediate Certificate ◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Sheet G001 states that registered design professional shall specify special inspections requirements but missing from the construction plan. Also missing special inspection certification documents with signatures. ◦ You may obtain the form at the following link: ◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf ◦ The Condition is added to the permit and then satisfied upon approval of the form. 2. 2018 California Building Code is referenced and used in structural calculation for City of Tucson, AZ project. (Applicable codes and references) 3. A702 – Detail 12 shows new concrete slab but such drawing is missing to show scope of work (2018 International Building Code section 107.2.1). Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:06:05 AM 1. Sheet G001/G002 – Adopted building codes missing applicable accessibility code for City of Tucson. 2. A101 - Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7). 3. A702 – Detail 11 is using 3x6 wood blocking for construction type ll-B noncombustible building. Explain and provide such applicable code exception section. 4. A703 – Partition detail 1 reference A101 for wall material specifications but missing from that sheet. 5. General – Provide response narrative to each review comments: building, structural, MPE, etc. Mechanical(M) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:27 AM 1. Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7). 2. M201 – Existing roof top units indicated but missing roof plan. Electrical(E) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:04:45 AM 1. E203 – Identify all cross reference electrical details in power or lighting plan such as typical slab penetration detail. This is described as one-story structure. Plumbing(P) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 11/17/2024 3:05:05 AM 1. Missing P102 new above ground plumbing plan listed in drawing index. 2. P201 – Residential code sections referenced in plumbing specifications. |
||
| 11/26/2024 | Fire New Construction | REQUIRES RESUBMIT | Resolve Safebuilt comments. Questions: patricia.shelton@tucsonaz.gov |
||
| 12/02/2024 | Site Engineering | REQUIRES RESUBMIT | TC-COM-1124-02208 9650 E 22ND ST Site engineering comments are as follows: 1. Please address the comments submitted by the SAFEbuilt reviewer. Ryan Insalaco ryan.insalaco@tucsonaz.gov |
||
| 11/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |