Permit Number: TC-COM-1124-02208
Parcel: 136406740

Address:
9650 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02208
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2024 Site Zoning APPROVED
12/10/2024 Water - PDSD APPROVED
12/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/18/2024 Commercial Electrical REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:46 AM
1. Special Inspections Intermediate Certificate
◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Sheet G001 states that registered design professional shall specify special inspections requirements but
missing from the construction plan. Also missing special inspection certification documents with signatures.
◦ You may obtain the form at the following link:
◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
◦ The Condition is added to the permit and then satisfied upon approval of the form.
2. 2018 California Building Code is referenced and used in structural calculation for City of Tucson, AZ project.
(Applicable codes and references)
3. A702 – Detail 12 shows new concrete slab but such drawing is missing to show scope of work (2018 International Building Code section 107.2.1).






Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:06:05 AM
1. Sheet G001/G002 – Adopted building codes missing applicable accessibility code for City of Tucson.
2. A101 - Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7).
3. A702 – Detail 11 is using 3x6 wood blocking for construction type ll-B noncombustible building. Explain and provide such applicable code exception section.
4. A703 – Partition detail 1 reference A101 for wall material specifications but missing from that sheet.
5. General – Provide response narrative to each review comments: building, structural, MPE, etc.






Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:27 AM
1. Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7).
2. M201 – Existing roof top units indicated but missing roof plan.







Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:04:45 AM
1. E203 – Identify all cross reference electrical details in power or lighting plan such as typical slab penetration detail. This is described as one-story structure.







Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:05 AM
1. Missing P102 new above ground plumbing plan listed in drawing index.
2. P201 – Residential code sections referenced in plumbing specifications.
11/18/2024 Commercial Mechanical REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:46 AM
1. Special Inspections Intermediate Certificate
◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Sheet G001 states that registered design professional shall specify special inspections requirements but
missing from the construction plan. Also missing special inspection certification documents with signatures.
◦ You may obtain the form at the following link:
◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
◦ The Condition is added to the permit and then satisfied upon approval of the form.
2. 2018 California Building Code is referenced and used in structural calculation for City of Tucson, AZ project.
(Applicable codes and references)
3. A702 – Detail 12 shows new concrete slab but such drawing is missing to show scope of work (2018 International Building Code section 107.2.1).






Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:06:05 AM
1. Sheet G001/G002 – Adopted building codes missing applicable accessibility code for City of Tucson.
2. A101 - Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7).
3. A702 – Detail 11 is using 3x6 wood blocking for construction type ll-B noncombustible building. Explain and provide such applicable code exception section.
4. A703 – Partition detail 1 reference A101 for wall material specifications but missing from that sheet.
5. General – Provide response narrative to each review comments: building, structural, MPE, etc.






Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:27 AM
1. Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7).
2. M201 – Existing roof top units indicated but missing roof plan.







Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:04:45 AM
1. E203 – Identify all cross reference electrical details in power or lighting plan such as typical slab penetration detail. This is described as one-story structure.







Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:05 AM
1. Missing P102 new above ground plumbing plan listed in drawing index.
2. P201 – Residential code sections referenced in plumbing specifications.
11/18/2024 Commercial Plumbing REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:46 AM
1. Special Inspections Intermediate Certificate
◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Sheet G001 states that registered design professional shall specify special inspections requirements but
missing from the construction plan. Also missing special inspection certification documents with signatures.
◦ You may obtain the form at the following link:
◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
◦ The Condition is added to the permit and then satisfied upon approval of the form.
2. 2018 California Building Code is referenced and used in structural calculation for City of Tucson, AZ project.
(Applicable codes and references)
3. A702 – Detail 12 shows new concrete slab but such drawing is missing to show scope of work (2018 International Building Code section 107.2.1).






Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:06:05 AM
1. Sheet G001/G002 – Adopted building codes missing applicable accessibility code for City of Tucson.
2. A101 - Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7).
3. A702 – Detail 11 is using 3x6 wood blocking for construction type ll-B noncombustible building. Explain and provide such applicable code exception section.
4. A703 – Partition detail 1 reference A101 for wall material specifications but missing from that sheet.
5. General – Provide response narrative to each review comments: building, structural, MPE, etc.






Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:27 AM
1. Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7).
2. M201 – Existing roof top units indicated but missing roof plan.







Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:04:45 AM
1. E203 – Identify all cross reference electrical details in power or lighting plan such as typical slab penetration detail. This is described as one-story structure.







Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:05 AM
1. Missing P102 new above ground plumbing plan listed in drawing index.
2. P201 – Residential code sections referenced in plumbing specifications.
11/18/2024 Commercial Structural REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:46 AM
1. Special Inspections Intermediate Certificate
◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Sheet G001 states that registered design professional shall specify special inspections requirements but
missing from the construction plan. Also missing special inspection certification documents with signatures.
◦ You may obtain the form at the following link:
◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
◦ The Condition is added to the permit and then satisfied upon approval of the form.
2. 2018 California Building Code is referenced and used in structural calculation for City of Tucson, AZ project.
(Applicable codes and references)
3. A702 – Detail 12 shows new concrete slab but such drawing is missing to show scope of work (2018 International Building Code section 107.2.1).






Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:06:05 AM
1. Sheet G001/G002 – Adopted building codes missing applicable accessibility code for City of Tucson.
2. A101 - Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7).
3. A702 – Detail 11 is using 3x6 wood blocking for construction type ll-B noncombustible building. Explain and provide such applicable code exception section.
4. A703 – Partition detail 1 reference A101 for wall material specifications but missing from that sheet.
5. General – Provide response narrative to each review comments: building, structural, MPE, etc.






Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:27 AM
1. Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices (2018 International Energy Conservation Code section C402.5.7).
2. M201 – Existing roof top units indicated but missing roof plan.







Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:04:45 AM
1. E203 – Identify all cross reference electrical details in power or lighting plan such as typical slab penetration detail. This is described as one-story structure.







Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 3:05:05 AM
1. Missing P102 new above ground plumbing plan listed in drawing index.
2. P201 – Residential code sections referenced in plumbing specifications.
11/26/2024 Fire New Construction REQUIRES RESUBMIT Resolve Safebuilt comments.
Questions: patricia.shelton@tucsonaz.gov
12/02/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1124-02208
9650 E 22ND ST

Site engineering comments are as follows:
1. Please address the comments submitted by the SAFEbuilt reviewer.
Ryan Insalaco
ryan.insalaco@tucsonaz.gov
11/15/2024 PDSD Application Completeness Express REVIEW COMPLETED