Permit Number: TC-COM-1124-02194
Parcel: 115080760

Address:
1247 N 7TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02194
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2024 Site Zoning APPROVED
12/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/22/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building or Structural Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please comply with Fire review comments. Additionally provide the longest total travel distance from within a room to the exit discharge at the bottom of the stairway. IBC 107.2.1
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/17/2024 Fire New Construction REQUIRES RESUBMIT -Please provide more information in the code analysis. A hotel is an R1 occupancy. You currently have hotel and R2 listed. Is it an R2 hotel with transient or nontransient occupants? I'm assuming the original use was hotel/R1 type of occupancy. A change in use could require fire sprinklers and fire alarm.
-Is it currently occupied? Is it being converted for long term housing (more than 30 days). Please provide more information on this project.
john.vincent@tucsonaz.gov
5203495581
11/29/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1124-02194
1247 N 7TH AV

1. A Floodplain Use Permit was issued for fire repair damage at this property on 11/20/23. Please confirm the scope & cost estimate is the same as documented under TE-FPU-1123-00388.

2. Please add the associated Floodplain Use Permit number on the plans.


Chris Arrington
chris.arrrington@tucsonaz.gov
12/03/2024 Design Review REVIEW COMPLETED If the Infill Incentive District (IID) will be pursued for the proposal, please contact me at maria.gayosso@tucsonaz.gov. Thank you.
11/14/2024 PDSD Application Completeness Express REVIEW COMPLETED