Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1124-02161
Parcel: 117110170

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02161
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2024 Historic NOT REQUIRED There are no historic-designated structures on site, so no historic preservation review is needed. If the IID will be pursued for this project, then SD-1124-00112 will need to be cancelled, and an IID Design Package will need to be submitted under a different SD Activity #, plus historic preservation review will be required. For historic preservation questions, please send an email to PDSDHistoric@tucsonaz.gov. Thank you.
12/06/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/19/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please amend the plans to provide the following Exterior Accessible Route information.
A. Delineate the primary path of travel to the area of work in accordance with 2009 ICC A117.1 402. Show a fully accessible route between all path of travel elements.
B. Specify the accessible route to be 5% maximum running slope with 2% maximum cross slope. 2009 ICC A117.1 403.3
C. Specify the gates on the accessible route comply with 2009 ICC A117.1 404
D. Please show the maneuvering clearance at the gates and specify the floor surface within the maneuvering clearances shall have a slope not steeper than 1:48 and shall comply with Section 302.
E. While one side of the gate will have panic hardware, please specify handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. 2009 ICC A117.1 404.2.6
F. Please specify a 10” kick plate on gate surface to create a smooth surface on the push side extending the full width of the door. Cavities created by added kick plates shall be capped. 2009 ICC A117.1 404.2.9
2. In the event one of the gates is not accessible, please provide directional signage indicating the route to the nearest like accessible element shall be provided at the following locations. These directional signs shall include the International Symbol of Accessibility and sign characters shall meet the visual character requirements in accordance with ICC A117.1. IBC 111.2
3. Please state on the plans the canopy is an approved covering that complies with one of the following, and additionally provide the manufacturer’s cutsheet: IBC 3105.3
A. The fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.
B. Has a flame spread index not greater than 25 when tested in accordance with ASTM E84 or UL 723.

C. Meets all of the following criteria when tested in accordance with NFPA 286:
i. During the 40 kW exposure, flames shall not spread to the ceiling.

ii. Flashover, as defined in NFPA 286, shall not occur.

iii. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

iv. The peak heat release rate throughout the test shall not exceed 800 kW.

4. Please provide the structural calculations sealed by an Arizona licensed design professional, used to design the canopy structure. IBC 3105.2

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
11/26/2024 Design Review REQUIRES RESUBMIT RNA Design Package under SD-1124-00112 will need to be accepted and approved before the construction documents can be approved. Any questions, please let us both know: Gabriel Sleighter (gabriel.sleighter@tucsonaz.gov) and maria.gayosso@tucsonaz.gov. Thank you.
11/22/2024 Fire New Construction REQUIRES RESUBMIT Resolve Commercial Structural comments.
Questions: patricia.shelton@tucsonaz.gov
12/06/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-1124-02161 - TD-DEV-1124-00303
177 N CHURCH AV. – OCR-2
Food Service – Outdoor Patio Expansion (1st Review)

TRANSMITTAL DATE: December 6, 2024

Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the OCR-2 zone (UDC 4.7.27). Food Service is an allowed use in the zone (UDC Table 4.8-4).

1. As Development Package (DP) TD-DEV-1124-00303 has not completed its first review Zoning cannot review the building plans for compliance with the DP and will review on the next submittal. Until the DP is approved by all review agencies Zoning cannot approve this building permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/12/2024 PDSD Application Completeness REVIEW COMPLETED
11/26/2024 Site Engineering REVIEW COMPLETED