Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1124-02160
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2024 | Site Zoning | APPROVED | |||
| 12/09/2024 | Water - PDSD | APPROVED | |||
| 12/09/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/25/2024 | Commercial Electrical | REQUIRES RESUBMIT | 1. Sheet E3.0 &E2.0 Detail the Electrical plans showing existing and new devices. Detail Lighting plan showing existing and new or relocated lights. | ||
| 11/25/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Sheet M1.0 Provide a Air Balance report to the inspector prior to the final inspection. | ||
| 11/25/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Sheet A1.1 Drinking fountain need to comply with the protruding objects section of ADAAG 2. Sheet P1.0 Show where the new floor sink is going to be tied into exiting waste line. Show pipe sizing and a detail for the trench repair. |
||
| 11/25/2024 | Commercial Structural | REQUIRES RESUBMIT | 1. Sheet A1.1 Will there be movable cubical walls installed in the bullpen? If so provide a layout to address egress | ||
| 11/26/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 11/12/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 11/26/2024 | Site Engineering | REVIEW COMPLETED |