Permit Number: TC-COM-1124-02153
Parcel: 11628001L

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02153
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2024 Site Zoning APPROVED
12/09/2024 Water - PDSD APPROVED
11/26/2024 Site Engineering NOT REQUIRED
12/02/2024 Site Landscape NOT REQUIRED
12/09/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
12/04/2024 Commercial Electrical REQUIRES RESUBMIT November 20, 2024
1st Review

Seaver Franks Architects
Attn: Rick Huch/Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT
ROOM REMODEL

City of Tucson Permit Number: TC-COM-1124-02153
Stantec Project Number: 185215066
Stantec File Number: TUC-24-143

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 204,551 TBD Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A0.0

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and the fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Please indicate if the type I construction indicated is A or B (protected or unprotected) in accordance with Table 601 of the 2018 International Building Code.

Sheet A2.6

1. Please indicate the wall type from the wall type schedule that will be provided for the infill of the connecting doors between rooms for room types D1 and K1.

Sheet A2.11

1. Please provide details indicating compliance with accessibility requirements for the new roll-in showers at the ADA rooms. [Ref. ICC A117.1-2009 Sec. 608]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance certificate for interior lighting. [Ref. IECC 2018 C405.3]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/04/2024 Commercial Mechanical REQUIRES RESUBMIT November 20, 2024
1st Review

Seaver Franks Architects
Attn: Rick Huch/Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT
ROOM REMODEL

City of Tucson Permit Number: TC-COM-1124-02153
Stantec Project Number: 185215066
Stantec File Number: TUC-24-143

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 204,551 TBD Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A0.0

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and the fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Please indicate if the type I construction indicated is A or B (protected or unprotected) in accordance with Table 601 of the 2018 International Building Code.

Sheet A2.6

1. Please indicate the wall type from the wall type schedule that will be provided for the infill of the connecting doors between rooms for room types D1 and K1.

Sheet A2.11

1. Please provide details indicating compliance with accessibility requirements for the new roll-in showers at the ADA rooms. [Ref. ICC A117.1-2009 Sec. 608]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance certificate for interior lighting. [Ref. IECC 2018 C405.3]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/04/2024 Commercial Plumbing REQUIRES RESUBMIT November 20, 2024
1st Review

Seaver Franks Architects
Attn: Rick Huch/Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT
ROOM REMODEL

City of Tucson Permit Number: TC-COM-1124-02153
Stantec Project Number: 185215066
Stantec File Number: TUC-24-143

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 204,551 TBD Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A0.0

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and the fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Please indicate if the type I construction indicated is A or B (protected or unprotected) in accordance with Table 601 of the 2018 International Building Code.

Sheet A2.6

1. Please indicate the wall type from the wall type schedule that will be provided for the infill of the connecting doors between rooms for room types D1 and K1.

Sheet A2.11

1. Please provide details indicating compliance with accessibility requirements for the new roll-in showers at the ADA rooms. [Ref. ICC A117.1-2009 Sec. 608]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance certificate for interior lighting. [Ref. IECC 2018 C405.3]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/04/2024 Commercial Structural REQUIRES RESUBMIT November 20, 2024
1st Review

Seaver Franks Architects
Attn: Rick Huch/Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT
ROOM REMODEL

City of Tucson Permit Number: TC-COM-1124-02153
Stantec Project Number: 185215066
Stantec File Number: TUC-24-143

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 204,551 TBD Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A0.0

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and the fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Please indicate if the type I construction indicated is A or B (protected or unprotected) in accordance with Table 601 of the 2018 International Building Code.

Sheet A2.6

1. Please indicate the wall type from the wall type schedule that will be provided for the infill of the connecting doors between rooms for room types D1 and K1.

Sheet A2.11

1. Please provide details indicating compliance with accessibility requirements for the new roll-in showers at the ADA rooms. [Ref. ICC A117.1-2009 Sec. 608]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance certificate for interior lighting. [Ref. IECC 2018 C405.3]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/26/2024 Fire New Construction REVIEW COMPLETED
11/12/2024 PDSD Application Completeness REVIEW COMPLETED