Permit Number: TC-COM-1124-02153
Parcel: 11628001L

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1124-02153
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2025 Site Zoning Standard APPROVED
04/29/2025 Water - PDSD Standard APPROVED
04/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/08/2025 Site Landscape Standard PENDING ASSIGNMENT
04/16/2025 Commercial Building Standard REQUIRES RESUBMIT April 16, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT
ROOM REMODEL (REVISIONS)

City of Tucson Permit Number: TC-COM-1124-02153
Stantec Project Number: 185215066
Stantec File Number: TUC-25-045

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 204,551 1,023 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A2.3

1. The ‘Overall Plan’ does not include hatched area locations referenced in the new legend for revised above lobby restrooms. Please clarify and revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

1. The plumbing plan-set is missing revised Sheets P1.00 and P1.10. Please provide.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/16/2025 Commercial Electrical Standard REQUIRES RESUBMIT April 16, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT
ROOM REMODEL (REVISIONS)

City of Tucson Permit Number: TC-COM-1124-02153
Stantec Project Number: 185215066
Stantec File Number: TUC-25-045

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 204,551 1,023 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A2.3

1. The ‘Overall Plan’ does not include hatched area locations referenced in the new legend for revised above lobby restrooms. Please clarify and revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

1. The plumbing plan-set is missing revised Sheets P1.00 and P1.10. Please provide.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/16/2025 Commercial Mechanical Standard REQUIRES RESUBMIT April 16, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT
ROOM REMODEL (REVISIONS)

City of Tucson Permit Number: TC-COM-1124-02153
Stantec Project Number: 185215066
Stantec File Number: TUC-25-045

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 204,551 1,023 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A2.3

1. The ‘Overall Plan’ does not include hatched area locations referenced in the new legend for revised above lobby restrooms. Please clarify and revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

1. The plumbing plan-set is missing revised Sheets P1.00 and P1.10. Please provide.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/16/2025 Commercial Plumbing Standard REQUIRES RESUBMIT April 16, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT
ROOM REMODEL (REVISIONS)

City of Tucson Permit Number: TC-COM-1124-02153
Stantec Project Number: 185215066
Stantec File Number: TUC-25-045

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 204,551 1,023 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A2.3

1. The ‘Overall Plan’ does not include hatched area locations referenced in the new legend for revised above lobby restrooms. Please clarify and revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

1. The plumbing plan-set is missing revised Sheets P1.00 and P1.10. Please provide.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/22/2025 Fire New Construction Standard REVIEW COMPLETED
04/08/2025 PDSD Application Completeness Express REVIEW COMPLETED