Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1124-02141
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/21/2024 | Commercial Electrical | APPROVED | |||
11/19/2024 | Commercial Structural | APPROVED | |||
11/19/2024 | Water - PDSD | APPROVED | |||
12/03/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/19/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Verify the amount of outside air introduced into the building. The outside air ventilation schedule shows 508 CFM of outside air is required but is calling for 505 CFM of outside air from each unit. This is excessively greater than the amount of air being exhausted from the building. Reference: Section 403.1, IMC 2018. 2. Provide general room exhaust for any cooking appliance (e.g. microwave oven) that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018. 3. Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018. |
||
11/19/2024 | Commercial Plumbing | REQUIRES RESUBMIT | The 3” horizontal branch serving the ice bin and dump sink (404 and 405) has a 2” cleanout. Cleanouts shall be sized per Section 708.1.7, IPC 2018. | ||
12/03/2024 | Design Review | REQUIRES RESUBMIT | Design professional recommends resubmittal. Review is attached to the permit, and may be accessed from TDC Online or through Property Research Online. If requested, staff can facilitate a meeting between the applicant team and design professional. Please email Maria Gayosso and myself at maria.gayosso@tucsonaz.gov and gabriel.sleighter@tucsonaz.gov Gabriel Sleighter -Lead Planner, PDSD |
||
11/26/2024 | Site Zoning | REQUIRES RESUBMIT | Final Site Zoning approval will be provided once the Historic and Design Review processes are complete. Historic and Design Review are required since it appears that changes to the exterior are included in this permit. No other Site Zoning issues were apparent during this review. | ||
11/17/2024 | Fire New Construction | REVIEW COMPLETED | |||
12/02/2024 | Historic | REVIEW COMPLETED | This project is in the Sunshine Mile UOD. No contributing historic buildings are to be demolished and proposal is mainly interior remodel. Per DP review, no historic adverse impacts. Any signage proposed will be subject to review. No historic concerns with the plans, If you have any questions, contact Michael.Taku@tucsonaz.gov |
||
11/07/2024 | PDSD Application Completeness | REVIEW COMPLETED | |||
11/22/2024 | Site Engineering | REVIEW COMPLETED |