Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1124-02141
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/19/2024 | Commercial Structural | APPROVED | |||
11/19/2024 | Water - PDSD | APPROVED | |||
N/A | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
N/A | Commercial Electrical | PENDING ASSIGNMENT | |||
N/A | Historic | PENDING ASSIGNMENT | |||
N/A | Site Engineering | PENDING ASSIGNMENT | |||
N/A | Site Zoning | PENDING ASSIGNMENT | |||
11/19/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Verify the amount of outside air introduced into the building. The outside air ventilation schedule shows 508 CFM of outside air is required but is calling for 505 CFM of outside air from each unit. This is excessively greater than the amount of air being exhausted from the building. Reference: Section 403.1, IMC 2018. 2. Provide general room exhaust for any cooking appliance (e.g. microwave oven) that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018. 3. Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018. |
||
11/19/2024 | Commercial Plumbing | REQUIRES RESUBMIT | The 3” horizontal branch serving the ice bin and dump sink (404 and 405) has a 2” cleanout. Cleanouts shall be sized per Section 708.1.7, IPC 2018. | ||
11/17/2024 | Fire New Construction | REVIEW COMPLETED | |||
11/07/2024 | PDSD Application Completeness | REVIEW COMPLETED |