Permit Number: TC-COM-1124-02141
Parcel: 12509012A

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02141
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2024 Commercial Structural APPROVED
11/19/2024 Water - PDSD APPROVED
N/A Bldg Permits - Post Review PENDING ASSIGNMENT
N/A Commercial Electrical PENDING ASSIGNMENT
N/A Historic PENDING ASSIGNMENT
N/A Site Engineering PENDING ASSIGNMENT
N/A Site Zoning PENDING ASSIGNMENT
11/19/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Verify the amount of outside air introduced into the building. The outside air ventilation schedule shows 508 CFM of outside air is required but is calling for 505 CFM of outside air from each unit. This is excessively greater than the amount of air being exhausted from the building. Reference: Section 403.1, IMC 2018.
2. Provide general room exhaust for any cooking appliance (e.g. microwave oven) that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.
3. Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.
11/19/2024 Commercial Plumbing REQUIRES RESUBMIT The 3” horizontal branch serving the ice bin and dump sink (404 and 405) has a 2” cleanout. Cleanouts shall be sized per Section 708.1.7, IPC 2018.
11/17/2024 Fire New Construction REVIEW COMPLETED
11/07/2024 PDSD Application Completeness REVIEW COMPLETED