Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1124-02130
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/03/2024 | Site Zoning | APPROVED | |||
12/05/2024 | Water - PDSD | APPROVED | |||
11/21/2024 | Site Engineering | NOT REQUIRED | |||
12/05/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/19/2024 | Commercial Building | REQUIRES RESUBMIT | November 8, 2024 1st Review Intertech Architecture Interiors, Inc. Attn: Erin Hastreiter 6089 E. Grant Road Tucson, Arizona 85716 Re: VIVIR MED SPA TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1124-02130 Stantec Project Number: 185215066 Stantec File Number: TUC-24-139 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B I-A 2,695 18 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A4 1. Please provide a seat in the accessible shower. [Ref. ICC A117.1-2009 Sec. 608.2.3.1] 2. The Restroom/Shower Plan is not to thew indicated scale of 3/16” = 1’. Please revise. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS General 1. The mechanical sheets are all marker “Preliminary Not For Construction”. Please provide final drawings for construction. PLUMBING COMMENTS General 1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 604] ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
11/19/2024 | Commercial Electrical | REQUIRES RESUBMIT | November 8, 2024 1st Review Intertech Architecture Interiors, Inc. Attn: Erin Hastreiter 6089 E. Grant Road Tucson, Arizona 85716 Re: VIVIR MED SPA TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1124-02130 Stantec Project Number: 185215066 Stantec File Number: TUC-24-139 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B I-A 2,695 18 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A4 1. Please provide a seat in the accessible shower. [Ref. ICC A117.1-2009 Sec. 608.2.3.1] 2. The Restroom/Shower Plan is not to thew indicated scale of 3/16” = 1’. Please revise. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS General 1. The mechanical sheets are all marker “Preliminary Not For Construction”. Please provide final drawings for construction. PLUMBING COMMENTS General 1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 604] ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
11/19/2024 | Commercial Mechanical | REQUIRES RESUBMIT | November 8, 2024 1st Review Intertech Architecture Interiors, Inc. Attn: Erin Hastreiter 6089 E. Grant Road Tucson, Arizona 85716 Re: VIVIR MED SPA TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1124-02130 Stantec Project Number: 185215066 Stantec File Number: TUC-24-139 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B I-A 2,695 18 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A4 1. Please provide a seat in the accessible shower. [Ref. ICC A117.1-2009 Sec. 608.2.3.1] 2. The Restroom/Shower Plan is not to thew indicated scale of 3/16” = 1’. Please revise. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS General 1. The mechanical sheets are all marker “Preliminary Not For Construction”. Please provide final drawings for construction. PLUMBING COMMENTS General 1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 604] ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
11/19/2024 | Commercial Plumbing | REQUIRES RESUBMIT | November 8, 2024 1st Review Intertech Architecture Interiors, Inc. Attn: Erin Hastreiter 6089 E. Grant Road Tucson, Arizona 85716 Re: VIVIR MED SPA TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1124-02130 Stantec Project Number: 185215066 Stantec File Number: TUC-24-139 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B I-A 2,695 18 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A4 1. Please provide a seat in the accessible shower. [Ref. ICC A117.1-2009 Sec. 608.2.3.1] 2. The Restroom/Shower Plan is not to thew indicated scale of 3/16” = 1’. Please revise. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS General 1. The mechanical sheets are all marker “Preliminary Not For Construction”. Please provide final drawings for construction. PLUMBING COMMENTS General 1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 604] ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
11/17/2024 | Fire New Construction | REVIEW COMPLETED | |||
11/06/2024 | PDSD Application Completeness | REVIEW COMPLETED |