Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1124-02130
Parcel: 12701005D

Review Status: In Review

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1124-02130
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2024 Site Engineering NOT REQUIRED
N/A Bldg Permits - Post Review PENDING ASSIGNMENT
N/A Site Zoning PENDING ASSIGNMENT
N/A Water - PDSD PENDING ASSIGNMENT
11/19/2024 Commercial Building REQUIRES RESUBMIT November 8, 2024
1st Review

Intertech Architecture Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85716

Re: VIVIR MED SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1124-02130
Stantec Project Number: 185215066
Stantec File Number: TUC-24-139

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B I-A 2,695 18 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A4

1. Please provide a seat in the accessible shower. [Ref. ICC A117.1-2009 Sec. 608.2.3.1]

2. The Restroom/Shower Plan is not to thew indicated scale of 3/16” = 1’. Please revise.

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

General

1. The mechanical sheets are all marker “Preliminary Not For Construction”. Please provide final drawings for construction.

PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/19/2024 Commercial Electrical REQUIRES RESUBMIT November 8, 2024
1st Review

Intertech Architecture Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85716

Re: VIVIR MED SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1124-02130
Stantec Project Number: 185215066
Stantec File Number: TUC-24-139

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B I-A 2,695 18 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A4

1. Please provide a seat in the accessible shower. [Ref. ICC A117.1-2009 Sec. 608.2.3.1]

2. The Restroom/Shower Plan is not to thew indicated scale of 3/16” = 1’. Please revise.

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

General

1. The mechanical sheets are all marker “Preliminary Not For Construction”. Please provide final drawings for construction.

PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/19/2024 Commercial Mechanical REQUIRES RESUBMIT November 8, 2024
1st Review

Intertech Architecture Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85716

Re: VIVIR MED SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1124-02130
Stantec Project Number: 185215066
Stantec File Number: TUC-24-139

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B I-A 2,695 18 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A4

1. Please provide a seat in the accessible shower. [Ref. ICC A117.1-2009 Sec. 608.2.3.1]

2. The Restroom/Shower Plan is not to thew indicated scale of 3/16” = 1’. Please revise.

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

General

1. The mechanical sheets are all marker “Preliminary Not For Construction”. Please provide final drawings for construction.

PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/19/2024 Commercial Plumbing REQUIRES RESUBMIT November 8, 2024
1st Review

Intertech Architecture Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85716

Re: VIVIR MED SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1124-02130
Stantec Project Number: 185215066
Stantec File Number: TUC-24-139

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B I-A 2,695 18 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A4

1. Please provide a seat in the accessible shower. [Ref. ICC A117.1-2009 Sec. 608.2.3.1]

2. The Restroom/Shower Plan is not to thew indicated scale of 3/16” = 1’. Please revise.

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

General

1. The mechanical sheets are all marker “Preliminary Not For Construction”. Please provide final drawings for construction.

PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/17/2024 Fire New Construction REVIEW COMPLETED
11/06/2024 PDSD Application Completeness REVIEW COMPLETED