Permit Number: TC-COM-1124-02129
Parcel: 133211120

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02129
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2024 Site Zoning APPROVED
11/18/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1124-02129
ADDRESS/PARCEL: (6602 E PASEO SAN ANDRES TUCSON, AZ 85710)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Not used
2. Group -Assisted living with behavioral services: (ensure that your selection confirms what you selected from the City Zoning Code & your State Department of Health Services License Application). Please enter this information in your Code Analysis. Include a statement as part of your code analysis as to how the facility handles any persons receiving custodial care who require limited verbal or physical assistance responding to an emergency situation to complete building evacuation and self preservation. Specify Condition 1 or Condition 2 per IBC 310 (this will determine the type of fire sprinkler system the fire department will require).
3. In an Emergency, show/locate the gathering area/dispersal area where it is safe from danger minimum 50 ft away from structure per IBC 310.5 and 1028.5.
4. The clear opening of the door to the accessible bathroom is 28 inches. Please propose a door with width that will comply to ICC/ANSI A117.
5. Not used
6. Not used
7. Not used
8. Fire Sprinkler is required per IBC 420 and processed as a separate permit. Submit the drawings to Tucson Fire Department for review and approval. They will conduct fire inspection, the inspection approval document will be required as a deferred submittal before issuing the Certificate of Occupancy.
9. Not used
10. Illumination with emergency backup power is required in all components of the means of egress system [IBC 1008]. Please locate/identify/label those equipment including the Emergency Light(s) w/ battery backup on your plan (to be inspected by Tucson Fire Department).
11. Electrical work (conductors/wiring/breaker ONLY) related to the installation will be inspected by City of Tucson inspectors, show on your plans so that our inspectors will know what wiring/breaker to inspect and shall also be reviewed as part of this permit.
12. Any new work must be included as part of this building permit.
13. A Final inspection will be conducted by our inspectors prior to issuance of the Certificate of Occupancy.
14. An Operator's License must be applied for with the State, the absence of this license shall void this building permit.
15. Not used
16. Please resubmit.
11/07/2024 Fire New Construction REQUIRES RESUBMIT Please clearly indicate on plan set as part of the R4 designation if all residents are Condition 1 or Condition 2, as this affects the fire sprinkler requirements. The current system is an NFPA 13D.
Questions: patricia.shelton@tucsonaz.gov
11/21/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1124-02129
6602 E PASEO SAN ANDRES

Site Engineering comments are as follows:
1. Please address Fire and Structural comments.

Ryan Insalaco
ryan.insalaco@tucsonaz.gov
11/06/2024 PDSD Application Completeness Express REVIEW COMPLETED