Permit Number: TC-COM-1124-02117
Parcel: 141185950

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1124-02117
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2024 Site Zoning APPROVED
12/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/13/2024 Commercial Building REQUIRES RESUBMIT Sheet G1.0 For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM)
1. Sheet G1.0 Should provide site plan for project identified in a multi suite building to verify all dimensions, required separations, property lines and access to building. Also will need to identify all utilities to building and location of new GI. Incomplete 2018 IBC 107..2.6 (BM)
2. Sheet G1.0 Provide for review, plumbing fixture calculation and schedule for all required fixtures based on provided occupant load. Incomplete 2018 IBC 107.2.1 (BM)
3. Sheet A1.0 Both restrooms identify CL dimension for water closets to be 1'7". Does not matched required dimensions identified on sheet G2.0. Clarify 2018 IBC 107.2.1 & ICC A117.1
4. Sheet A2.0 Identify existing exterior / egress door in schedule to include dimensions, locks and latches to comply with new occupancy in tenant space per 2018 IBC section 1010. Incomplete (BM)
5. Sheet A2.0 Provide for review, walk-in cooler wall, ceiling and installation data per manufacture. Incomplete 2018 IBC 107.2.1 (BM)
11/13/2024 Commercial Electrical REQUIRES RESUBMIT 1. Sheet E1.0 Identify complete existing SES to supply three or more suites as identified. Provide complete Data for SES type, ampacity, voltage, main and meters. Incomplete 2018 IBC 107.2.1 (BM)
11/13/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Sheet M2.0 Identify height of parapet wall at roof edge to comply with minimum guard height or provide detail for guard to comply with 2018 IMC 304.11 (BM)
2. Sheet M2.0 Keyed note #8 identified at WIC, is not noted at HVAC keyed note schedule, clarify 2018 IBC 107.2.1 (BM)
11/13/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Sheet P1.0 Note #2 in plumbing fixture schedule should also note an access door for hard lids identified at restroom ceiling. Clarify 2018 IPC 606.3 (BM)
2. Sheet P2.0 Natural gas calculation note #1 should be 2018 IFGC for adopted code per City of Tucson (BM)
3. Sheet P2.0 clouded note for domestic water systems, CW piping noted to be PVC, will need to correct to comply with 2018 IPC table 605.4, PVC not listed for within building. (BM)
4. Sheet P3.0 Provide detail with notes for sediment trap to be installed at WH gas supply with trap downstream of SOV. 2018 IFGC 408.4 (BM)
5. SheeP3.1 Plan fixture schedule and plans identify an IWH, detail 5 for storage tank WH should be removed from plans unless added to fixture schedule and plans as an option. 2018 IBC 107.2.1 (BM)
11/18/2024 Water - PDSD REQUIRES RESUBMIT PVC is not approved for use in a water distribution system within a building (see boxed note on P2.0). Reference: Section 605.4, IPC 2018.
11/08/2024 Fire New Construction REVIEW COMPLETED
11/05/2024 PDSD Application Completeness Express REVIEW COMPLETED
11/20/2024 Site Engineering REVIEW COMPLETED