Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1124-02116
Parcel: 12701005D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1124-02116
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2024 Water - PDSD APPROVED
11/29/2024 Site Zoning NOT REQUIRED
12/02/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/19/2024 Commercial Building REQUIRES RESUBMIT November 14, 2024
1st Review

Intertech Architectural Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: 14TH FLOOR RESTROOM
REMODEL

City of Tucson Permit Number: TC-COM-1124-02116
Stantec Project Number: 185215066
Stantec File Number: TUC-24-137

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 13,382 90 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. The remodeled bathrooms do not meet the requirements for accessible toilet rooms. It does appear that the bathrooms are technically infeasible to alter to meet accessibility requirements. In this case, a family or assisted-use toilet room shall be located on the same floor and in the same area as the existing toilet rooms. [Ref. IEBC 2018 Sec. 305.8.10] {Joel is aware that there are specific floors located in this building that include accessible bathrooms. It may be more practical to use these existing accessible bathrooms to meet the section mentioned above with an appeal to the building official for approval.}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/19/2024 Commercial Electrical REQUIRES RESUBMIT November 14, 2024
1st Review

Intertech Architectural Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: 14TH FLOOR RESTROOM
REMODEL

City of Tucson Permit Number: TC-COM-1124-02116
Stantec Project Number: 185215066
Stantec File Number: TUC-24-137

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 13,382 90 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. The remodeled bathrooms do not meet the requirements for accessible toilet rooms. It does appear that the bathrooms are technically infeasible to alter to meet accessibility requirements. In this case, a family or assisted-use toilet room shall be located on the same floor and in the same area as the existing toilet rooms. [Ref. IEBC 2018 Sec. 305.8.10] {Joel is aware that there are specific floors located in this building that include accessible bathrooms. It may be more practical to use these existing accessible bathrooms to meet the section mentioned above with an appeal to the building official for approval.}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/19/2024 Commercial Mechanical REQUIRES RESUBMIT November 14, 2024
1st Review

Intertech Architectural Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: 14TH FLOOR RESTROOM
REMODEL

City of Tucson Permit Number: TC-COM-1124-02116
Stantec Project Number: 185215066
Stantec File Number: TUC-24-137

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 13,382 90 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. The remodeled bathrooms do not meet the requirements for accessible toilet rooms. It does appear that the bathrooms are technically infeasible to alter to meet accessibility requirements. In this case, a family or assisted-use toilet room shall be located on the same floor and in the same area as the existing toilet rooms. [Ref. IEBC 2018 Sec. 305.8.10] {Joel is aware that there are specific floors located in this building that include accessible bathrooms. It may be more practical to use these existing accessible bathrooms to meet the section mentioned above with an appeal to the building official for approval.}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/19/2024 Commercial Plumbing REQUIRES RESUBMIT November 14, 2024
1st Review

Intertech Architectural Interiors, Inc.
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: 14TH FLOOR RESTROOM
REMODEL

City of Tucson Permit Number: TC-COM-1124-02116
Stantec Project Number: 185215066
Stantec File Number: TUC-24-137

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 13,382 90 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. The remodeled bathrooms do not meet the requirements for accessible toilet rooms. It does appear that the bathrooms are technically infeasible to alter to meet accessibility requirements. In this case, a family or assisted-use toilet room shall be located on the same floor and in the same area as the existing toilet rooms. [Ref. IEBC 2018 Sec. 305.8.10] {Joel is aware that there are specific floors located in this building that include accessible bathrooms. It may be more practical to use these existing accessible bathrooms to meet the section mentioned above with an appeal to the building official for approval.}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/07/2024 Fire New Construction REVIEW COMPLETED
11/04/2024 PDSD Application Completeness REVIEW COMPLETED
11/19/2024 Site Engineering REVIEW COMPLETED