Permit Number: TC-COM-1124-02104
Parcel: 11007159A

Address:
4253 E FLOWER ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02104
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2024 Site Engineering APPROVED
11/27/2024 Site Zoning APPROVED
12/05/2024 Water - PDSD APPROVED
12/05/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2024 Commercial Electrical REQUIRES RESUBMIT
11/14/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Sheet M2.00, 2018 IMC 504; Provide clothes dryer exhaust detail. DMA
11/14/2024 Commercial Plumbing REQUIRES RESUBMIT
11/14/2024 Commercial Structural REQUIRES RESUBMIT Sheet c0.01; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review is NOT within the scope of this review. All applicable comments will be followed with the initials, DMA.
1. Sheet C0.01, 2018 IBC 1107.6.2.2.1 Type A units. In Group R-2 occupancies containing more than 20 dwelling units or sleeping units, at least 2 percent but not less than one of the units shall be a Type A unit. ALL Group R-2 units on a SITE shall be considered to determine the total number of units and the required number of Type A units. Type A units shall be dispersed among the various classes of units. Provide Type A and B calculation and dispersion. DMA
2. Sheet g0.07, 2018 IBC 714.2 Installation. A listed penetration firestop system shall be installed in accordance with the manufacturer’s installation instructions and the listing criteria. Provide on the plans the listing and installation instructions for firestop systems. DMA
3. Sheet S1.0, 2018 IBC Ch 17; Provide Tucson Special Inspection Certificate. DMA
4. Sheet S1.0; Submit referenced Saeco soils report for this review. DMA
11/17/2024 Fire New Construction REVIEW COMPLETED
11/01/2024 PDSD Application Completeness Express REVIEW COMPLETED