Permit Number: TC-COM-1124-02101
Parcel: 10511061Q

Address:
4420 N STONE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02101
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2024 Site Zoning APPROVED
11/27/2024 Water - PDSD APPROVED
11/27/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/14/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/14/2024 2:59:48 PM




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 11/14/2024 2:53:08 PM
1. Sheet A3/Occupant Load Calculation: The occupant load calculation is incorrect. There are booths present that have not been accounted for. Provide an updated space by space occupant load calculation in accordance with 2018 IBC Section 1004.3, 1004.6 and Table 1004.5.
2. Sheet A3/Travel Distances: The egress plans do not indicate the travel distances. Provide the maximum travel distances for this space in accordance with 2018 IBC Section 1017.2.
3. Sheet A8/Exit lighting: The reflected ceiling plan does not indicate the location of exit lighting. Provide the location of exit lighting in accordance with 2018 IBC Section 1013.
4. Sheet A8/Egress Illumination: The reflected ceiling plan does not indicate the location of egress illumination. Provide the location of egress illuminatino in accordance with 2018 IBC Section 1013.





Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 11/14/2024 2:58:19 PM
1. General: Please demonstrate compliance with the 2018 International Energy Conservation Code (2018 IECC), ◦ The available options are to meet the prescriptive requirements of 2018 IECC Chapter 4; meet the requirements of the 2016 edition of AHRI/ASHRAE 90.1 (Energy Standard for Buildings Except Low-rise Residential Buildings) or an energy analysis of the proposed building. (2018 IECC Section 401.2)
◦ COMcheck is accepted alternative to compliance. COMcheck is a free energy conservation compliance software through the U.S. Department of Energy (US DOE) and is available online at www.energycodes.gov/rescheck.
2. General: Provide all manufacturer specifications for the new Type I hood system.






Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/14/2024 2:58:03 PM






Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/14/2024 2:59:41 PM
11/07/2024 Fire New Construction REVIEW COMPLETED
11/01/2024 PDSD Application Completeness REVIEW COMPLETED
11/18/2024 Site Engineering REVIEW COMPLETED