Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1123-02768
Parcel: 11521017H

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1123-02768
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
02/06/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 2/5/2024 5:40:24 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 2/2/2024 1:06:35 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 2/5/2024 10:32:17 AM
1. General - Provide Commercial Energy Calculations/Mechanical Compliance Certificate - Heat Load Calculations - 2018 International Energy Conservation Code Sections C402 & C403 (RESOLVED)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 12/12/2023 2:38:47 PM
Electrical Review of Bianchi’s Italian Restaurant
By: Ron Ross PE
E4.1 SINGLE-LINE DIAGRAM/CALCS:

Comments only.

Wire sized on Shour circuit calculation table (F3 and F4) is #10 vs one line and panel schedule call out for #12. Either size results in acceptable values.

Primary Circuit breaker and secondary Fuse protection for Buck-Boost step up xfmr could be upsized. Current design could result in nuisance trip.