Permit Number: TC-COM-1123-02767
Parcel: 13321158E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1123-02767
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2023 Site Zoning APPROVED
01/03/2024 Site Engineering NOT REQUIRED
01/04/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/04/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.

Please amend plans to show the same number of exterior doors at the front of the building on all sheets. Sheet A102 shows one exterior door at the front while A103 shows two exterior doors at the front of the building. IBC 107.2.1

Please amend plans to provide illumination for the means of egress, including the exit discharge per IBC 1008. Show compliance with the following:

A. The means of egress shall be illuminated at all times the building space is occupied.

B. The means of egress illumination level shall not be less than 1 foot-candle at the walking surface.

C. The means of egress illumination shall be supplied by backup power (consisting of storage batteries, unit equipment, or an on-site generator) for a duration of not less than 90 minutes. IBC 1008.3

3. Please amend plans to show how this building meets the accessibility requirements of 2018 chapter 11. For example, Accessible Entrance, Accessible Toilet room, Signage, etc.

Mark Masek

Plans Examiner

Mark.masek@tucsonaz.gov

520-837-4994
12/11/2023 Fire New Construction REVIEW COMPLETED
12/06/2023 PDSD Application Completeness Express REVIEW COMPLETED