Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-1123-02764
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/04/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/04/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The previous electrical plans review comments are not completely addressed. 1a. Per the total lumen calculation shown, 104,343 lumens per acre, this will require a special inspection per OLC section 106.2.1. The total lumens exceed 100,000 lumens per acre. Provide a note on the plans per OLC section 104.2.2. 1b. Be advised the Outdoor Lighting Special Inspection Certificate must be filled out including the first registrant seal and submitted for review prior to approval of plan review. See City of Oro Valley or Pima County Development services website to download a list of acceptable Outdoor Lighting Special Inspectors. 2. Please check the lumen calculations. Per the luminaire quantities and lumen outputs shown in the luminaire schedule, the total lumens do not compute to 104,343 lumens. Show exactly how the calculated lumens totaled 104,343 lumens. 3. The lumen output for unshielded exterior luminaires cannot exceed 3000 lumens per luminaire. OLC section 401.4. ‘LSWS’. 4. Provide compliance for unshielded luminaire curfew requirements and timer controls as required per OLC section 403.1, 403.5 5. Provide full compliance with the 2018 IECC for the interior and exterior lighting as applicable. Do not confuse the IECC with the OLC. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code (OLC). |
||
12/26/2023 | PDSD Application Completeness | REVIEW COMPLETED |