Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1123-02762
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/04/2024 | Site Engineering | NOT REQUIRED | |||
12/19/2023 | Site Zoning | NOT REQUIRED | |||
01/04/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/02/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Please provide the ICC ESR Evaluation Report for the Fiber-Reinforced Polymer Reinforcing Bars to be used in this repair. IBC 107.2.1 2. Provide the ICC ESR Evaluation Report or other approved evaluation report for the 6000 psi repair mortar. IBC 107.2.1 4. Please amend plans to indicate the same values in the Stem wall Repair note #11 and the stem wall detail section A-A/Page 3. as note#11 indicated 2500psi concrete and detail indicates 6000 psi repair mortar. IBC 107.2.1 5. Please provide an approved special inspector with applicable special inspector approval as this special inspector could only be found as approved for UL fire stopping. IBC 1704.2.1 Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994 |
||
12/06/2023 | PDSD Application Completeness | REVIEW COMPLETED |