Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2024 Site Engineering NOT REQUIRED
12/19/2023 Site Zoning NOT REQUIRED
01/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/02/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Please provide the ICC ESR Evaluation Report for the Fiber-Reinforced Polymer Reinforcing Bars to be used in this repair. IBC 107.2.1
2. Provide the ICC ESR Evaluation Report or other approved evaluation report for the 6000 psi repair mortar. IBC 107.2.1
4. Please amend plans to indicate the same values in the Stem wall Repair note #11 and the stem wall detail section A-A/Page 3. as note#11 indicated 2500psi concrete and detail indicates 6000 psi repair mortar. IBC 107.2.1
5. Please provide an approved special inspector with applicable special inspector approval as this special inspector could only be found as approved for UL fire stopping. IBC 1704.2.1