Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1123-02757
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/13/2023 | Site Zoning | APPROVED | |||
12/20/2023 | Water - PDSD | APPROVED | |||
01/02/2024 | Commercial Mechanical | NOT REQUIRED | |||
12/29/2023 | Site Engineering | NOT REQUIRED | |||
01/02/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/27/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Provide complete compliance with the 2018 IECC for the lighting. 2. Modified branch circuits shall be legibly identified in the panel schedule as to its clear, evident, and specific purpose and use. NEC 408.4. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC. |
||
12/21/2023 | Commercial Plumbing | REQUIRES RESUBMIT | What will be connected to the water supply shown on sheet P100? Reference: Section 107.2.1, IBC 2018. | ||
01/02/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. As this building has more than one occupancy classification, please identify the mixed occupancy methodology as either nonseparated, separated, or a stated combination of types. IBC 508.1 2. Please amend the Code review to indicate the Actual Number of Stories of each building is shown and indicate the story this project is located in. IBC 503.1 3. Please indicate the penetration locations in walls and floors are and reference where to find information. IBC 714.1 4. Details for penetration firestops are provided, if penetrations are being made in rated floor, wall and ceiling assemblies. The entire approved firestop assembly is to be shown on the drawings. IBC 714.1 5. Please amend plans to provide test reports for curtains and fabric hangings called out by keynote 4/A401 meet the requirements of 806.4 6. Please amend the plans to indicate a readily visible durable sign is posted on the egress side on or adjacent to the main door stating: THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background. IBC 1010.1.9.4-2.2 7. Please provide engineering to show how unbraced interior walls and partitions that exceed 6 feet in height, including their finish materials, shall have adequate strength and stiffness to resist the loads to which they are subjected but not less than a horizontal load of 5 psf. IBC 1607.15. Additionally, provide design and calculations to show how Detail F8/A101 resists gravity and lateral loads. Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994 |
||
12/27/2023 | Fire New Construction | REVIEW COMPLETED | |||
12/04/2023 | PDSD Application Completeness | REVIEW COMPLETED |