Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1123-02732
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/04/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The drawing submitted showing the ‘Fire Affected Area’ states, “Electrical Repaire Inside Unit Are Complete”.

Provide a detailed description of the scope of electrical repairs completed. Verify that replaced Luminaires and devices meet 2017 NEC requirements.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
11/29/2023 PDSD Application Completeness Express REVIEW COMPLETED