Permit Number: TC-COM-1123-02691
Parcel: 132131100

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1123-02691
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2024 Water - PDSD APPROVED
06/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/10/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 3/21/2024 10:54:56 AM
Structural review is approved. Subject to the field inspector's approval.


Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 5/6/2024 8:22:42 AM
1) Unresolved - Sheet G0.0: Include all allowed vs actual building area, height, and number of stories. Include the areas under the roof/canopy, cooler, and trash enclosures. List all codes used in the design. (2018 IBC section 107) The actual
building height, number of stories, and total building area are still not included in the allowed vs actual under ‘Building Limitations”. Please show the total actual building area of the restaurant and canopy along with the areas of the accessory structures shown separately. The 2018 IECD listed in the “Applicable Building Codes” is not a code standard. **The restaurant building area (including the canopy and cooler) is not shown separately from the trash enclosures. The allowed building height is still not shown. **

2) Unresolved - Sheets 5/14, SU1.1, SU1.2 (Site Plans): The revised additional canopy is still not shown on the site plan sheet 5 of 14. (2018 IBC section 107)

3) Resolved - Sheet S0.0: Provide the shear wall plans. 2018 IBC section 1603.1)

4) Resolved - Sheet A1.2: The incorrect egress loading table and sections are stated for the 2018 IBC. (2018 IBC section 1004, Table 1004.5)

5) Resolved - Sheet A2.1: Include the roof storm water drainage calculations. (2018 IPC Chapter 11)

6) Resolved - Sheet A5.1: Show the toilet centerline distance from the side wall: (2009 ICC A117.1 section 604.2) The toilet center line is to be a maximum of 18” from the side wall – please revise.

7) Resolved - Sheet M1: Specify if the mechanical room is heated space. Show the mechanical room heat source, duct insulation or room insulations as applicable. (2018 IECC sections C402, C403.11)

8) Unresolved – Sheet A1.2: The occupant load was revised to include the patio dining area and was not correctly calculated. Dining areas are to be calculated at 1 person per 15 sf. The occupant load used in the design was not consistent
– 6 occupants were calculated (incorrect), service areas were increased to 10, egress calculations used 24 occupants, plumbing calculations used 20 occupants. Please correct and revise all affected sheets and calculations. (2018 IBC section
1004)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 5/6/2024 8:23:51 AM
Mechanical pans are approved.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 5/6/2024 8:23:27 AM
Electrical plans are approved



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 5/6/2024 8:24:40 AM
1) Resolved - Sheet M1: Show the vents for each fixture and the drain and vent sizes for each fixture. (2018 IPC section 106.3.1) Many floor sinks, mop sink, and lavatory do not show the individual drain pipe sizes. The amended 2018 IPC section
1003.3 requires grease interceptor discharge venting.

2) Resolved - Sheets M1.1, M2.1, E1.1: Include the grease interceptor and interceptor vents on the layout and isometric plans. The floor sinks and hand sinks are to be connected to the grease interceptor. A sign stating “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” is to be posted if the hand wash sink is not connected to the grease interceptor. Please coordinate and revise the calculations and details on the plans. (2018 IPC section 1003.3) The MEP plans do not match the revised plans showing separation of the toilet room from opening directly into the kitchen per 2018 IPC section 403.3.2.

3) Resolved - Sheet M3.1: Provide the faucet specifications showing compliance with the requirements of 2018 IPC sections 412.11, 419.6)

4) Resolved - Sheet E1.1: Show the air handler unit disconnects, cooler lights, receptacle, and disconnect. (2017 NEC sections 210.63, 210.70, 440.11)

5) Unresolved – Sheet A1.2: The occupant load was revised to include the patio dining area and was not correctly calculated. Dining areas are to be calculated at 1 person per 15 sf. The occupant load used in the design was not consistent – 6 occupants were calculated (incorrect), service areas were increased to 10, egress calculations used 24 occupants, plumbing calculations used 20 occupants. Please correct and revise all affected sheets and calculations. (2018 IPC section)
05/30/2024 Site Engineering REQUIRES RESUBMIT 1. The building permit cannot be approved until the associated development package, TD-DEV-0823-00380, has been approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
06/03/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-1123-02691
960 East Tucson Marketplace Boulevard – PAD-15
Food Service (3rd Review)

TRANSMITTAL DATE: June 3, 2024

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

1. Zoning has reviewed the building plans for compliance with the associated development package TD-DEV-0823-00380. Although it appears the building plan footprint and square footage are consistent with the submitted development package, Zoning cannot approve TC-COM-1123-002691 until the development package is approved by all reviewers.

2. Except for the Utility sheet the DP sheets submitted in the building plans shall either be the stamped approved plans, or marked as for reference only, or removed from the plan set.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/01/2024 PDSD Application Completeness REVIEW COMPLETED