Permit Review Detail
Review Status: Approved
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1123-02678
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/27/2023 | External Reviewers - Willdan | APPROVED | Approved As Noted: 1. Hi/Lo DF spouts will need to meet ADA height requirements. 2. All new boxes and conduits installed in existing rated walls will need to maintain rated wall integrity. Box installation will need to meet membrane penetration requirements. (Typical at all locations) 3. Fan support will need to be listed and capable of supporting fans from structure and installed as per manufactures requirements. 4. Required min working clearance per NEC 110.26 will need to be maintained including Door and frame parts in open position. 5. H1 Lighting will need to be coordinated with sprinkler and FA elements within space. |
||
| 11/28/2023 | Site Zoning | APPROVED | |||
| 12/11/2023 | Water - PDSD | APPROVED | |||
| 12/15/2023 | Site Engineering | NOT REQUIRED | |||
| 12/15/2023 | Bldg Permits - Post Review Express | REVIEW COMPLETED | |||
| 11/27/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 11/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |