Permit Number: TC-COM-1123-02678
Parcel: 10408005D

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1123-02678
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2023 External Reviewers - Willdan APPROVED Approved As Noted:
1. Hi/Lo DF spouts will need to meet ADA height requirements.
2. All new boxes and conduits installed in existing rated walls will need to maintain rated wall integrity. Box installation will need to meet membrane penetration requirements. (Typical at all locations)
3. Fan support will need to be listed and capable of supporting fans from structure and installed as per manufactures requirements.
4. Required min working clearance per NEC 110.26 will need to be maintained including Door and frame parts in open position.
5. H1 Lighting will need to be coordinated with sprinkler and FA elements within space.
11/28/2023 Site Zoning APPROVED
12/11/2023 Water - PDSD APPROVED
12/15/2023 Site Engineering NOT REQUIRED
12/15/2023 Bldg Permits - Post Review Express REVIEW COMPLETED
11/27/2023 Fire New Construction REVIEW COMPLETED
11/17/2023 PDSD Application Completeness Express REVIEW COMPLETED