Permit Number: TC-COM-1123-02677
Parcel: 128010190

Address:
110 S WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1123-02677
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/04/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 12/1/2023 12:50:29 PM
See the building review comments.




Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 12/1/2023 12:49:12 PM
1) Sheet CS: The building and canopy areas scaled on the plans do not match the area shown in the project data. (2018 IBC section 107)

2) Sheet GN2.0: Correct accessibility floor level notes #2 and #3 per 2009 ICC A!17.1 section 303.

3) Sheet S0.1: The design needs to use a wind speed of 105 mph for risk category II. (2018 IBC amended section 1609.1.1)

4) Sheet S3.1: Include the roof framing details for the hood grease duct. The duct is shown in the location of a truss. (2018 IBC section 107)

5) Sheets P2, P3, and P4: Floor sinks and hand wash sinks are not connected to the grease interceptor. A sign stating “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” is to be located at each hand wash
sink not connected to the grease interceptor. Please revise all affected sheets and details. (2018 IPC amended section 1003.3)

6) Sheet E2: The electrical equipment room is missing an emergency light. (2018 IBC section 1008.3.3)

7) Sheet E4: All kitchen receptacles are to be GFCI protected. (2017 NEC section 210.8(B)(2) and (5))




Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 12/1/2023 12:49:59 PM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 12/1/2023 12:49:46 PM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 12/1/2023 12:50:12 PM
See the building review comments.
12/15/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
12/04/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1123-02677
110 S WILMOT RD – C-1
Food Service (1st Review)

TRANSMITTAL: December 4, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Food Service: Excluding Soup Kitchens is a allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-1122-00049, but it does not appear that the plans match. This building plan shows a square footage of 1,241 on sheet AS1.0 and the DP was approved on a square footage of 1,067. Either the building plans will need to be changed to match the DP or a revision to the DP is required.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/12/2023 Water - PDSD REQUIRES RESUBMIT Clarify the intended size of the water meter. The domestic water calculations on P2 show both a 1” meter and a 1-1/2” meter. The plumbing site plan on P1 shows a 1” water meter. Reference: Section 107.2.1, IBC 2018.
11/22/2023 Fire New Construction REVIEW COMPLETED
11/21/2023 PDSD Application Completeness REVIEW COMPLETED