Permit Number: TC-COM-1123-02668
Parcel: 10511061R

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1123-02668
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2024 Bldg Permits - Post Review REVIEW COMPLETED
01/17/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 1/15/2024 2:30:38 PM



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 1/11/2024 4:12:01 PM
The building review is approved. Subject to the field inspector's approval.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 11/28/2023 5:13:16 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/30/2023 9:52:01 AM
Electrical Review of Victorias Secret
By: Ron Ross PE

Permit is approved, comments below should be addressed/incorporated in Bid set.

E02.02: Could not locate Keyed Note 29

E02.51: Keyed Note 13 is used.

E04.02: Detail F description outside of box.

E05.02: Missing Electrical lighting controls sheet per sheet index.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 1/16/2024 6:10:46 PM
Second Plumbing Review:OK

Resolved-1). Need to address Bldg plan review comment 1 -IPC 403.3.1

Resolved-2). plan page P01.01 shows an additional instantaneous water heater on the fixture schedule, that doesn't correlate with plumbing plan piping illustrations? -IPC 106.3.1

**Instantaneous water heater not to be used per response comments**