Permit Number: TC-COM-1123-02668
Parcel: 10511061R

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1123-02668
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2024 Site Zoning APPROVED
04/30/2024 Water - PDSD APPROVED
04/24/2024 Site Engineering NOT REQUIRED
04/30/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/09/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 4/5/2024 11:35:01 PM



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 4/3/2024 8:34:27 AM
1. General: Show the revised design and area details on all affected sheets. Include the changes in the scope of work, increase of tenant and work floor area, occupant calculations, add S-1 use group, separation wall rating, etc. on the cover sheet. Include the new and existing details for lighting, emergency lighting, means of egress routes, exit signs, sprinklers, fire alarms, fixtures and shelving, reflected ceiling plans, finishes, add the new door in the door schedule, changes to the key plans, accessibility details, etc. as needed for the new scope of work and additional space included in the project. (2018 IBC section 107)


Mechanical N/A

Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 4/1/2024 4:32:29 PM
1. Need to coordinate RTU-1 electrical OCP and conductor feeds to support Mechanical revision change as called out on sheet M01.01 Rooftop Heat Pump Schedule 'Electrical'.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 4/9/2024 2:44:47 PM
Revised plan Plumbing Review:
1). Plan Sheet P03.01: lift tank detail is missing the shut off valve. Add the required shut off valve on the discharge side of the check valve in accordance with -2018 IPC 712.2 First Plumbing Review
04/01/2024 Fire New Construction REVIEW COMPLETED
04/01/2024 PDSD Application Completeness REVIEW COMPLETED